Nailor 37S Manual page 125

Low profile fan powered terminal unit with epic ecm or psc motor
Table of Contents

Advertisement

ANALOG CONTROL CALIBRATION CHARTS
VOLTAGE VS. AIRFLOW
When field adjustment or field calibration of the CTE-5100 series thermostats is necessary, desired limit control can be calculated using the
tables in Figure 3 and the following formulas, or the charts presented in Figures 4 through 8.
Formulas:
CFM = K (VDC - Offset)
Follow the individual calibration procedure for the thermostat model(s) as required.
Inlet size
K factor
4 in. Round
33
5 in. Round
55
6 in. Round
75
7 in. Round
115
8 in. Round
143
9 in. Round
175
10 in. Round
233
12 in. Round
357
14 in. Round
500
16 in. Round
625
Figure 3. Diamond Flow Sensor K Factors.
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0
0
Figure 4. Inlet Sizes 4, 5, 6 Round
3/11 IOM-AECVAV
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
VDC = (CFM/K) + Offset
Offset
Inlet size
+ 0.44
12 in. Oval
+ 0.02
14 in. Oval
+ 0.08
16 in. Oval
- 0.19
18 in. Oval
+ 0.32
+ 0.10
Inlet size
+ 0.09
- 0.04
- 0.07
- 0.25
SIZ E
4
1 0 0
2 0 0
K factor
333
417
588
759
K factor
14 x 10
417
24 x 16
1250
S I ZE
S I ZE
5
6
3 0 0
AIRFLOW, CF M
Offset
- 0.22
- 0.47
+ 0.05
- 0.27
Offset
- 0.14
- 0.07
4 0 0
5 0 0
6 0 0
Page 3 of 10