OHM ELECTRIC COOL CABI OCA-H300BC-AW2 Instruction Manual page 47

Table of Contents

Advertisement

6-
Assignment of alarm output terminals
Once an alarm is detected, the alarm output contact changes over.
By setting the alarm output terminals, monitoring of many different operations is enabled. Each setting functions by
changing the parameters AS and Ao
Before supplying power to COOLCABI, both of terminals - and -3 are open. The time lag between power input
and the changeover of the terminals is .8 seconds.
Monitoring of alarm occurrence [AS: ]
The state of alarm output terminals changes by alarm occurrence regardless of whether cooling operation is
performed or not.
Monitoring of cooling operation and alarm occurrence [AS: ]
The state of alarm output terminals changes responding to the state of cooling operation and alarm occurrence.
3 Identifying alarms that require power input and alarms that do not [AS: ]
The state of alarm output terminals changes responding to the alarms E , E3, E4, E6, E7 S , S , S3 and S4
that are restored automatically or manually and the alarms E5, E8, S5, tE and SE that require power
reconnection.
4
Identifying alarms that continue cooling operation and alarms that do not
The state of alarm output terminals changes responding to the alarms E , E4, S , S , S3 and S4 that continue
cooling operation and the alarms E3, E5, E6, E7, E8, S5, tE and SE that do not.
*Cooling operation means the state that the compressor is working and cool air is being output from the discharge port.
Between terminals 1 and 2
AS
Description
Contact changes over by
0
the state of an alarm
Contact changes over by
1
the state of an alarm
Contact changes over by
the state of an alarm that
2
requires power
reconnection
Contact changes over by
the state of an alarm that
3
discontinues cooling
operation
Between terminals 1 and 2
AS
Description
Contact changes over by
0
the state of an alarm
Contact changes over by
1
the state of an alarm
Contact changes over by
the state of an alarm that
2
requires power
reconnection
Contact changes over by
the state of an alarm that
3
discontinues cooling
operation
Remarks *3: Alarm E4 is not output when
See page 43 .
【Default】
Assignment table of alarm output terminals [Ao: 0]
COOLCABI
Contacts
Alarm OFF
CLOSE
Alarm ON
OPEN
Alarm OFF
OPEN
Alarm ON
CLOSE
E5, E8, S5, tE, SE
OPEN
Alarm OFF
E5, E8, S5, tE, SE
CLOSE
Alarm ON
E3, E5, E6, E7,
E8, S5, tE, SE
OPEN
Alarm OFF
E3, E5, E6, E7,
E8, S5, tE, SE
CLOSE
Alarm ON
Assignment table of alarm output terminals [Ao: 1]
COOLCABI
Contacts
Alarm OFF
OPEN
Alarm ON
CLOSE
Alarm OFF
CLOSE
Alarm ON
OPEN
E5, E8, S5, tE, SE
CLOSE
Alarm OFF
E5, E8, S5, tE, SE
OPEN
Alarm ON
E3, E5, E6, E7,
E8, S5, tE, SE
CLOSE
Alarm OFF
E3, E5, E6, E7,
E8, S5, tE, SE
OPEN
Alarm ON
is set at
[AS:3]
Between terminals 2 and 3
Description
Contact changes over by
the state of an alarm
Contact changes over by
the state of cooling
operation
Contact changes over by
the state of an alarm that
does not require power
reconnection
Contact changes over by
the state of an alarm that
continues cooling
operation
Between terminals 2 and 3
Description
Contact changes over by
the state of an alarm
Contact changes over by
the state of cooling
operation
Contact changes over by
the state of an alarm that
does not require power
reconnection
Contact changes over by
the state of an alarm that
continues cooling
operation
See page 43
47
COOLCABI
Contacts
Alarm OFF
OPEN
Alarm ON
CLOSE
Cooling operation
OPEN
is stopped
In cooling operation
CLOSE
E1, E3, E4
, E6,
*3
E7, S1, S2, S3, S4
OPEN
Alarm OFF
E1, E3, E4
, E6,
*3
E7, S1, S2, S3, S4
CLOSE
Alarm ON
E1, E4
*3
S1, S2, S3, S4
OPEN
Alarm OFF
E1, E4
*3
S1, S2, S3, S4
CLOSE
Alarm ON
COOLCABI
Contacts
Alarm OFF
CLOSE
Alarm ON
OPEN
Cooling operation
OPEN
is stopped
In cooling operation
CLOSE
E1, E3, E4
*3
, E6,
E7, S1, S2, S3, S4
CLOSE
Alarm OFF
E1, E3, E4
, E6,
*3
E7, S1, S2, S3, S4
OPEN
Alarm ON
E1, E4
*3
S1, S2, S3, S4
CLOSE
Alarm OFF
E1, E4
*3
S1, S2, S3, S4
OPEN
Alarm ON