5-3 Change of Setting temperature
It is basically recommended to maintain the initial set value of 35℃. Setting at an unnecessarily low
value may cause excessive condensation and excess amount of drainage water.
Turn on the COOLCABI. The current internal temperature is displayed.
Press the SET button. The current setting temperature is displayed with flashing.
3 Change the setting temperature using the Up and Down buttons within the range between 3 ℃ to 45℃.
actory setting: 35℃
4 Press the SET button to save the setting. The current internal temperature is displayed again.
5-4
orced cooling operation for inspection purpose
Hold down the Up and Down buttons at the same time for more than 3 seconds.
The operation lamp blinks and COOLCABI starts forced cooling operation. After the amount of time set by the
parameter elapses, COOLCABI will return to normal operation.
Note: Factory setting for forced cooling operation is 60 seconds.
5-5 Parameter setting
enerally, there is no need to change the setting of parameters. If necessary, follow the procedures described
below.
○Hold down the SET button for more than 3 seconds when an internal temperature is displayed.
Parameters are displayed in the following order. Press the SET button to move to the next parameter.
Display the parameter desired to be changed and set the value using the Up and Down buttons. Press the
SET button to save the change.
・Differential d
This indicates the temperature difference against setting temperature at which the compressor stops.
Caution: Setting of the temperature and the differential value should be made so as to avoid
・ orced cooling operation time Cd
This is to set the time of forced cooling operation which is executed when the Up and Down buttons
are pressed for more than 3 seconds at the same time.
・High temperature alarm AL
This is to set the temperature at which High temperature alarm E
・Differential for High temp. alarm dA
This is the differential value for resetting High temp. alarm.
The alarm is cancelled when the temperature reaches the value of AL minus dA.
・Maintenance reminder
This is the function to remind you of maintenance works in a timely manner.
Time measurement in the control board is made on an hour basis. As an example, if this is set to
99, notification is made in 99
・ orced cooling operation setting at power input CS
This is to set whether forced cooling operation is carried out at the time of power input.
・Setting for restoration method from Overheat Pr
Select
Caution
When Auto reset is selected, cooling operation will restart if the overheat detector in the refrigerant circuit is reset.
However, the contact output and the alarm code indication are not reset. Repeating auto reset without eliminating
the root cause may result in product failure. Early maintenance is recommended.
Default: 5℃
repetition of compressor's on off operation of 6 or more times in an hour.
Default: 45℃
I
Default: 0
: This function is unused
to 99:
represents
: Not carry out forced cooling operation at power input
: Carry out forced cooling operation at power input
or
for setting how to restore from Overheat E3 .
:Manual reset
See page 46
:Auto reset
Caution
Setting range: 3 to
Default: 6 (60 sec)
Setting range: 35 to 5 ℃
Default: 2℃
Setting range:
Setting range:
hours. Outputs notification at the set time.
hours after power input.
Default:0
Default: 0
)
42
Setting range:
to 3
outputs.
to
to 99
Setting range: ,
Setting range: ,
to 3