Tyco MULTIMATIC F470H Manual page 9

Deluge valve, horizontal
Table of Contents

Advertisement

1 - 300 lb. Water
32 - 1/2" x 3" Nipple
Pressure
33 - 1/2" x 5" Nipple
Gauge (2 req'd)
34 -1/2" x 7-1/2"
2 - 1/4" Gauge
35 - 1/2" x 10-1/2"
Test Valve
Nipple for
3 - Model F180
4" valve,
Manual Control
1/2" x 12"
Station
Nipple for
4 - 2" Angle Valve
6" valve
5 - 1/2" Ball Valve
36 - 1/4" x 4" Nipple
(2 req'd)
37 - 2 x 3" Nipple
6 - 1/2" Swing
38 - 2 x 4" Nipple
Check Valve
7 - 1/2" Spring
Loaded Check
Valve
D1 - Model B-1
8 - Priming Supply
Dry Pilot
Restriction
Actuator
9 - 1/2" Y-Strainer
D2 - 250 lb. Air
10 - Model F793
Pressure Gauge
Automatic
D3 - 1/4" Gauge
Drain Valve
Test Valve
11 - Drip Funnel
D4 - 1/2" Globe
Support Plug
Valve
12 - Drip Funnel
D5 - 1/4" Pressure
Support
Relief Valve
13 - Drip Funnel
D6 - 1/4" Plug
14 - 3/32" Vent
D7 - 1/2" Tube
Fitting
Connector
15 - 1/2" Angle
D8 - 1/2" Tube,
Valve
30" long
16 - 1/4" Tube,
D9 - 1/2" 90° Elbow
30" long
(2 req'd)
17 - 1/2" Tube,
D10 - 1/2" x 1/2" x 1/4"
Connector
Tee (2 req'd)
18 - 1/2" Tube,
D11 - 1/2" Tee (2 req'd)
24" long
D12 - 1/4" x 2" Nipple
19 - 1/4" Plug
D13 - 1/2" x close
20 - 1/2" Plug
Nipple (2 req'd)
21 - 3/4" Plug
D14 - 1/2" x 1-1/2"
22 - 1/2" Union
Nipple (4 req'd)
(5 req'd)
D15 - 1/2" x 2"
23 - 1/2" 90° Elbow
Nipple (2 req'd)
(3 req'd)
24 - 1/2" Tee (4 req'd)
25 - 1/2" x 1/4" x 1/2"
Tee (2 req'd)
E1 - 1/2" 90° Elbow
26 - 1/2" x 1/2" x 3/4"
E2 - 1/2" Tube
Tee
Connector
27 - 1/2" Cross
E3 - 1/2" Tube,
28 - 1/2" x 1/4"
30" long
Bushing
E4 - 1/2" x 1-1/2"
29 - 2" 90° Elbow
Nipple
30 - 1/2" x 1-1/2"
(2 req'd)
Nipple
E5 - 24VDC Solenoid
(16 req'd)
Valve
31 - 1/2" x 2"
Nipple
NOTES:
1. Wet Pilot Actuation Trim consists of
Items 1 through 38.
2. Dry Pilot Actuation Trim consists of
Items 1 through 38 plus Items D1
through D15.
3. Electric Actuation Trim consists of
Items 1 through 38 plus Items E1
through E5.
4. The nipples utilized in the trim ar-
rangements are Schedule 40 steel
per ASTM A53 or A135 and they are
threaded per ANSI B1.20.1 The fit-
tings are either malleable iron per
ANSI B16.3 or cast iron per ANSI
B16.4.
"Standard order" trim is provided
with black nipples and fittings: how-
ever, galvanized nipples and fittings
are available on "special order".
VALVE TRIM
BILLS OF MATERIALS
auxiliary drains in the system. Close
the auxiliary drain valves after water
ceases to discharge. Leave the Main
Drain Valve open.
4. Depress the plunger of the Automat-
ic Drain Valve to verify that it is open
and that the F470H Valve, as well as
the horizontal main, is completely
drained.
5. Remove the Handhole Cover and
thoroughly clean all interior parts of
the F470H Valve. Make certain that
the two 1/8 inch (3,2mm) diameter
pressure equalizing vents in the sys-
tem side of the Clapper are open.
Test the Clapper, Clapper Latch, and
Flange and Push Rod for freedom of
movement. Inspect the Clapper Fac-
ing for any sign of deterioration due
to age or chemicals in the water.
Replace worn or damaged parts, ac-
cordingly.
6. Raise the Clapper and pivot the
Clapper latch to allow the Clapper to
be reseated. After reseating the
Clapper, release the Latch so that it
reseats on the Clapper.
7. Clean the Strainer in the Diaphragm
Chamber Supply connection by re-
moving the clean-out plug and
strainer basket. The Strainer may be
flushed out by momentarily opening
the Diaphragm Chamber Supply
Control Valve.
8. Open the Alarm Control Valve (Fig.
D), if it was closed to silence local
alarms.
It is recommended that the Alarm
Control Valve be wire sealed in the
open position with a No. 16 twisted
wire, the ends of which are secured
by a lead seal. The wire seal should
be looped through the hole in the
handle and tightly twisted around the
pipe nipple adjacent to the handle.
9. Reset the actuation system.
Manual Actuation — Push the oper-
ating lever up; however, do not close
the hinged cover at this time.
Wet Pilot Actuation — Replace op-
erated pilot sprinklers and/or reset
the manual control stations.
Dry Pilot Actuation — Replace oper-
ated pilot sprinklers and/or reset the
manual control stations. Re-estab-
lish dry pilot pneumatic pressure.
Electric Actuation — Reset the elec-
tric detection system in accordance
with the manufacturer's instructions
to de-energize the solenoid valve.
NOTE
If the system is being set after a
fire and in order to prevent the
-9-
possibility of a subsequent opera-
tion of an overheated solder type
pilot sprinkler, any solder type pi-
lot sprinklers which were possibly
exposed to a temperature greater
than their maximum rated ambi-
ent must be replaced.
10. Open the Diaphragm Chamber Sup-
ply Control Valve and allow time for
full pressure to build up in the Dia-
phragm Chamber.
11. Operate (open) the Manual Control
Station to vent trapped air from the
Diaphragm Chamber. If necessary,
first open the hinged cover, and then
fully pull down on the operating lever.
SLOWLY close the operating lever,
by pushing it up, after aerated water
ceases to discharge from the Man-
ual Control Station drain tubing.
Close the hinged cover and insert a
new break rod in the small hole
through the top of the enclosing
box.
If wet pilot actuation is being used,
crack open the Inspector's Test Con-
nection and any other vent valves, to
relieve trapped air. After the dis-
charge of air has stopped, close the
vent valves and the Inspector's Test
Connection.
12. Inspect drain connections from the
Manual Control Station, Solenoid
Valve, Dry Pilot Actuator, and Alarm
Devices, as applicable. Any leaks
must be corrected before proceed-
ing to the next step.
13. Replace the Handhole Cover and
Gasket. Tighten all Handhole Cover
Bolts uniformly using a cross-draw
sequence.
14. Slowly open the Main Control Valve.
Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, the F470H Valve is ready
to be placed in service and the Main
Control Valve must then be fully
opened.
NOTE
After setting a fire protection system,
notify the proper authorities and ad-
vise those responsible for monitoring
proprietary and/or central station
alarms.