Tyco DV-5A Manual

Tyco DV-5A Manual

Automatic water control valve, single interlock preaction, electric actuation, fire protection systems 1 1/2 to 8 inch (dn40 to dn200)
Hide thumbs Also See for DV-5A:

Advertisement

Quick Links

DV-5
Automatic Water Control Valve, Single
a
Interlock Preaction, Electric Actuation, Fire Protec-
tion Systems 1 1/2 to 8 Inch (DN40 to DN200)
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/dv-5a-auto-
si-pre-act-fire-pro-8-dn40-200
General
Description
The TYCO DV-5
Automatic Water
a
Control Valve Single Interlock Preaction
Electric Actuation is a diaphragm type
valve that can be used in single inter-
lock preaction fire protection systems.
When properly trimmed, the double
seat design of the DV-5
a
provides actuation of fire alarms upon
system operation.
The diaphragm style design of the
DV-5
Valve allows external resetting,
a
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
Page 1 of 18
End Connection
Inlet
Outlet
Thread
Thread
Groove
Groove
Flange
Groove
Flange
Flange
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5
a
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5
Valve also
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5
a
tion Electric Actuation Valve is offered
with or without a System Main Control
Valve.
Available End Connections and Weights — lb (kg)
1 1/2
2
(40)
(50)
26
25
(11,8)
(11,3)
25
25
(11,3)
(11,3)
N/A
N/A
N/A
N/A
features internal and exter-
in cor-
a
Single Interlock Preac-
JUNE 2022
Worldwide
www.tyco-fire.com
Contacts
Nominal Valve Size
ANSI Inches
(DN)
3
4
6
(80)
(100)
(150)
N/A
N/A
N/A
60
95
177
(27,2)
(43,1)
(80,3)
66
106
190
(30,0)
(48,1)
(86,2)
72
116
204
(32,7)
(52,6)
(92,5)
The DV-5
Single Interlock Preaction
a
Electric Actuation Valve utilizes auto-
matic sprinklers and a supplemental
detection system, comprised of electric
detection comprised of heat detectors,
smoke detectors, and manual pull sta-
tions. Actuation of the detection system
automatically operates (releases) the
DV-5
Valve, allowing water to flow
a
into the sprinkler piping system and to
be discharged from any sprinklers that
may subsequently open.
165,1
8
mm
(200)
N/A
N/A
177
327
(80,3)
(148,3)
346
N/A
(157,0)
365
N/A
(165,6)
TFP1421

Advertisement

Table of Contents
loading

Summary of Contents for Tyco DV-5A

  • Page 1 The DV-5 Single Interlock Preaction Simply re-pressurizing the diaphragm Electric Actuation Valve utilizes auto- The TYCO DV-5 Automatic Water chamber resets the valve. matic sprinklers and a supplemental Control Valve Single Interlock Preaction detection system, comprised of electric...
  • Page 2 TFP1421 Page 2 of 18 Nominal Valve Size ANSI Inch (DN) Item Description Qty. 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) Valve Body Diaphragm 545000020 545000020 545000030 545000040 545000060 545000080 Diaphragm Cover Hex Bolt, Short 545100001 545100001 545100002...
  • Page 3 TFP1421 Page 3 of 18 Port Sizes, NPT Inch per ANSI B1.20.1 Port Port Description 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) Diaphragm Chamber Supply Water Supply Pressure & Alarm Test Alarm Actuation Automatic Drain Valve System Drain Main Drain 1 1/4...
  • Page 4: Technical Data

    FM Approved sprinkler system because the system Listing and Approvals are based on will have essentially filled with water DV-5a Single Interlock Preaction Elec- 10-3/16" before a sprinkler operates. The DV-5 tric Actuation Valve being trimmed as (260 mm) Single Interlock Preaction Electric described in Figure 5.
  • Page 5: Materials Of Construction

    TFP1421 Page 5 of 18 FLOW RATE IN LITERS PER MINUTE (LPM) (1 GPM = 3,785 LPM) 1000 2000 3000 5000 7000 10000 15000 0,600 0,500 0,400 0,300 0,200 0,100 0,090 0,080 0,070 0,060 0,050 0,040 0,030 0,022 1000 2000 3000 4000 FLOW RATE IN GALLONS PER MINUTE (GPM)
  • Page 6: Operation

    Model MRA-1 Manual Reset Actuator Dimensions are provided in Figure 7. opens to constantly vent the DV-5 Dia- The TYCO DV-5 Valve is a diaphragm Notes: phragm Chamber to hydraulically latch style valve that depends upon water The normally closed, de-energized,...
  • Page 7: Installation

    Step 2. The DV-5 Single Interlock Pre- Step 10. A desiccant dryer, when action Electric Actuation Valve must be DV-5A Automatic Water Control Valves required for the supervisory air supply, are designed to be used in freshwater trimmed in accordance with the trim is to be installed between a drip leg illustration shown in Figure 5.
  • Page 8 TFP1421 Page 8 of 18 1-1/2" (DN40) AND 2" (DN50) Assemble in order VALVES ONLY from A to L Notes: 1. Port Connections P1 through P7 are described in Figure 2. 2. External Trim Connections C1 through C5 are described in Figure 8. 3.
  • Page 9 Item A7 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180. 4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A9 1-1/2" (DN40) AND 2" (DN50) are separately ordered, as ap- VALVES ONLY plicably related to valve size.
  • Page 10 545003005 545003005 LABEL WIRE — — — — — — DV-5 VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS WATERFLOW PRESSURE ALARM SWITCH, 25710 25710 25710 25710 25710 25710 PS10-2 (AMER/APAC) WATERFLOW PRESSURE ALARM SWITCH, 0260...
  • Page 11 TFP1421 Page 11 of 18 Nominal Inches Valve (mm) Size ANSI Inches (DN) 1 1/2 10.4 15.7 16.2 10.2 8.02 (40) (71) (246) (264) (399) (411) (185) (259) (204) (31) 10.4 15.7 16.2 10.2 8.09 (50) (71) (246) (264) (399) (411) (185) (259)
  • Page 12 Perform Steps 1 through 16 when ini- drain tube, slowly close the operating (F) for leaks. If there are leaks, deter- tially setting the TYCO DV-5 Electric lever by pushing it up. Do not close the mine/correct the cause of the leakage Actuation Valve, after an operational hinged cover at this time.
  • Page 13 TFP1421 Page 13 of 18 Item Description Item Description External Trim Connections DV-5 Valve System Gauge Diaphragm Supply Connection System Main Control Valve Manual Control Station Water Motor Alarm Connection Waterflow Pressure Switch Manual Reset Actuator Supervisory Air Supply Connection Main Drain Valve Diaphragm Supply Valve Waterflow Pressure Alarm Switch...
  • Page 14: Care And Maintenance

    TFP1421 Page 14 of 18 Care and Drop in Water Supply Pressure Supervisory Low Pressure Alarm Below Normal Range Test Procedure Maintenance Proper operation of the Supervisory NOTICE Low Pressure Switch (U) must be per- formed as follows: If the water supply pressure is signif- The following procedures and inspec- icantly reduced below the normally tions must be performed as indicated,...
  • Page 15 Valve (F). Step 5. Using the union, secure the leakage. MRA-1 Manual Reset Actuator (N) to Use only TYCO replacement fasteners the Diaphragm Cover. as specified in Figure 1. Step 6. Using the union, secure the Do not apply adhesives, lubricants, or Electric Actuation Trim.
  • Page 16 1 1/2 in. (DN40) ....550061315 DV-5A Valves with Galvanized Trim 2 in. (DN50) ....550061320...
  • Page 17 4 in. (DN100)....530040040 DV-5 Valve Replacement Parts DV-5A Valves with Galvanized Trim 6 in. (DN150)....530040060 Specify: (Description) for use with...
  • Page 18 TFP1421 Page 18 of 18 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...