Requirements Specific To Perforated Cabinets - Cisco MDS 9200 Series Installation Manual

Cisco systems hub/switch installation guide
Hide thumbs Also See for MDS 9200 Series:
Table of Contents

Advertisement

Cabinet and Rack Requirements
S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m
The cabinet or rack must also meet the following requirements:
Note

Requirements Specific to Perforated Cabinets

A perforated cabinet is defined here as a cabinet with perforated front and rear doors and solid side walls.
In addition to the requirements listed in the
page
A perforated cabinet that conforms to these requirements is available from Rittal Corporation:
Cisco MDS 9200 Series Hardware Installation Guide
A-2
The minimum vertical rack space per chassis must be three RU (rack units), equal to 5.25 in. (13.3
cm).
The width between the rack-mounting rails must be at least 17.75 in. (45.1 cm) if the rear of the
switch is not attached to the rack. For four-post EIA racks, this is the distance between the two front
rails.
For four-post EIA cabinets (perforated or solid-walled):
The minimum spacing for the bend radius for fiber-optic cables should have the front mounting
rails of the cabinet offset from the front door by a minimum of 3 in. (7.6 cm), and a minimum
of 5 in. (12.7 cm) if cable management brackets are installed on the front of the chassis.
The distance between the outside face of the front mounting rail and the outside face of the back
mounting rail should be 23.5 to 34.0 in. (59.7 to 86.4 cm) to allow for rear bracket installation.
A minimum of 2.5 in. (6.4 cm) of clear space should exist between the side edge of the chassis
and the side wall of the cabinet. No sizeable flow obstructions should be immediately in the way
of chassis air intake or exhaust vents.
Optional jumper power cords are available for use in a cabinet. See the
section on page
C-11.
A-1, perforated cabinets must meet the following requirements:
The front and rear doors must have at least a 60 per cent open area perforation pattern, with at least
15 square inches of open area per rack unit of door height.
Cisco recommends that the roof be perforated with at least a 20 percent open area.
Cisco recommends an open or perforated cabinet floor to enhance cooling
Rittal Corporation
One Rittal Place
Springfield, OH 45504
Contact: (800) 477–4220
Cabinet P/N: Rittal 9969427
Cabinet description: PS-DK/OEM Cabinet Assembly, (78.7 in.) 1998 mm X 23.6 in. (600 mm) X
39.4 in. (1000 mm) (H x W x D) (42 RU)
Appendix A
"General Requirements for Cabinets and Racks" section on
Cabinet and Rack Installation
"Jumper Power Cord"
.
OL-19588-01

Advertisement

Table of Contents
loading

Table of Contents