Replacement Components (For Qualified Service Personnel Only) - Viessmann KK10 Installation, Start-Up And Service Instructions Manual

Boiler control unit for high temperature heating systems
Table of Contents

Advertisement

Additional Information
Replacement Components
Fuse, Part No. 7815 580
Fixed high limit, Part No. 7819 411
20
(for qualified service personnel only)
F1: T 6.3 A / 250 V, slow blow
for control operation
H Electro-mechanical temperature limit
with liquid filled capillary
H Safety feature: if capillary is not
liquid tight (leaks), switch deactivates
IMPORTANT
Due to the expansion characteristics of
the liquid contained in the capillary, the
switch also deactivates (opens) at 14°F /
-10°C thereby shutting down the heating
system.
H Sets a maximum limit for boiler water
temperature whereafter the switch
deactivates and locks
(factory setting 230°F / 110°C)
H H H H Adjustable to 212°F / 100°C via slot
screw
on rear side (readjustment
to previous position is not possible)
WARNING
If adjusting to 212°F / 100°C, AHL
must not be set higher than 167°F /
75°C.