Viessmann KK10 Installation, Start-Up And Service Instructions Manual page 23

Boiler control unit for high temperature heating systems
Table of Contents

Advertisement

Boiler Protection
90 ºF/32 ºC
149 ºF/65 ºC
216 ºF/104 ºC
Fig. 1
Minimum setting shaft position
216 ºF/104 ºC
183 ºF/
84 ºC
118 ºF/
60 ºF/
48 ºC
16 ºC
90 ºF/32 ºC
Fig. 2
Pump aquastat label
(continued)
Minimum Boiler Temperature Setting
Boiler control without DHW pump module
Minimum
temperature setpoint
104 to 113 ºF/
40 to 45 ºC
No minimum
temperature
Boiler control with DHW pump module
Minimum
temperature setpoint
104 to 113 ºF/
40 to 45 ºC
No minimum
temperature
PA Pump aquastat
1
The Vitola 200 boiler does not have a boiler-mounted pump junction box.
When the Vitotronic, KK10 control is used with the DHW pump module, the factory default
setting will allow the space heating pump and the DHW pump to turn off when the boiler
water temperature is below the minimum boiler temperature setpoint. This function is
disabled when the S1.6 DIP switch setting is changed from the OFF position to the ON
position (upward movement of the DIP switch).
Minimum Temperature Setpoint Adjustment
The minimum boiler water temperature setpoint can be adjusted to a higher boiler
water temperature. This may be useful in applications using high temperature
heating circuits.
To determine whether an increase in minimum boiler water temperature setpoint is
recommended for your application, read the following information.
Minimum boiler water temperature by boiler
Boiler model
Vitola 200
Vitorond 200
Vitogas 050, RS
Vitogas 100, GS1
Vitogas 100, GS10
To adjust the minimum temperature for the Vitotronic, KK10 control, turn the
pump aquastat up or down. Use one of the following guidelines when modifying
the temperature as desired:
-Refer to Fig. 1 on the left.
-Use scale inside the control.
When the control is opened, the aquastat is located at the front of the control. The
vintage of the control will dictate the presence of an aquastat label
(see Fig. 2). If no label is present, look for the end shaft as illustrated in Fig. 1.
DIP switch S1.4
Burner operation
position
ON
Enabled when boiler
water temp. below
PA setting
OFF
Not enabled
No minimum
DIP switch S1.4
Burner operation
position
ON
Enabled when boiler
water temp. below
PA setting
OFF
Not enabled
No minimum
Fuel type
Oil/Gas
Oil
Gas
Gas
Gas
Additional Information
Boiler pump
connected via pump
junction box
Pump off when
boiler water temp.
below PA setting
Pump off when
boiler water temp.
below PA setting
Boiler pump
connected via DHW
pump module
Pump off when
boiler water temp.
1
below PA setting
Pump off when
boiler water temp.
1
below PA setting
Minimum boiler temperature
No minimum
104 ºF/40 ºC
120 ºF/49 ºC
104 ºF/40 ºC
120 ºF/49 ºC
23