Viessmann KK10 Installation, Start-Up And Service Instructions Manual page 21

Boiler control unit for high temperature heating systems
Table of Contents

Advertisement

Replacement Components
Adjustable high limit, Part No. 7819 316
Other replacement components (not shown)
Description
Temperature gage, °F
Temperature gage, °C
Temperature gage, °C / °F
LED circuit board
Pump aquastat
(for qualified service personnel only)
Additional Information
H Electro-mechanical temperature limit
with liquid filled capillary
H Controls maximum boiler water
temperature
(Factory setting 167°F / 75°C)
H Adjustable to 189, 203 and 212°F /
87, 95 and 100°C by breaking off
tabs
enabling dial to rotate right to
desired maximum temperature.
WARNING
AHL setting must be at least 36°F /
20°C higher that DHW tank
temperature.
IMPORTANT
The AHL must not be set higher than
167°F / 75°C if the FHL is set to
212°F / 100°C.
Quantity
Part No.
1
7334 598
1
7334 599
1
9543 566
1
1
9525 828