Normal Led Operation; Ic695Cep001 Leds; Figure 4: Cep001 Leds - GE PACSystems RX3i User Manual

Cep profinet scanner
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Chapter 2. LED Operation and Connectors

2.1 Normal LED Operation

IC695CEP001 LEDs

Power LEDs
The RX3i CEP001 Carrier has two Power LEDs, PWR1 and PWR2 that indicate whether the power is applied and
is within range corresponding to the two power sources.
Green, ON
OFF
OK LED
The OK LED indicates whether the CEP001 Carrier is able to perform normal operation.
Green, ON
Amber, ON
Amber, blink pattern
Fast blinking
OFF
Connect LED
The CONN LED indicates the status of PROFINET connections.
Green, ON
Amber, blink pattern
Amber, blink in 1Hz
OFF
18

Figure 4: CEP001 LEDs

Power is applied at the minimum specified level
Power supply does not have power or has failed
RX3i CEP001 is OK
Either the RX3i CEP001 Carrier or I/O module has a fault
Fatal error- flashes once between error codes
CEP001 has no valid MAC addresses
CEP001 has an unrecoverable fault
At least one PROFINET connection (AR) exists with an IO-Controller
Fatal error- flashes once between error codes blinked on the OK LED
No device name configured
No PROFINET connection (AR) exists
PACSystems* RX3i CEP PROFINET Scanner
GFK-2883E

Advertisement

Table of Contents
loading

Table of Contents