Maximum heating capacity and power consumption
HWT-401HW-E
Power (kW)
TO (°C)
Power
consumption (kW)
TO (°C)
Coefficient of perfor-
mance (COP)
TO (°C)
▪ Heating capacity and power consumption at maximum heating capacity
▪ Heating capacity and power consumption at maximum compressor speed
▪ Power consumption without water pump
▪ Heating capacity and power consumption are measured according to EN 14511
TO:
Outdoor temperature (TK°C)
VLT:
Supply water temperature (°C)
30
-20
3.22
-15
3.91
-10
4.57
-7
4.96
-2
5.89
2
6.64
7
7.39
10
8.11
12
8.53
15
8.76
20
9.13
30
-20
1.22
-15
1.32
-10
1.38
-7
1.37
-2
1.37
2
1.37
7
1.33
10
1.31
12
1.31
15
1.31
20
1.31
30
-20
2.64
-15
2.97
-10
3.30
-7
3.62
-2
4.31
2
4.86
7
5.58
10
6.19
12
6.51
15
6.68
20
6.97
VLT (°C)
35
40
3.10
2.98
3.73
3.55
4.40
4.23
4.80
4.64
5.70
5.51
6.42
6.21
7.25
7.11
7.95
7.80
8.42
8.26
8.63
8.47
8.98
8.83
VLT (°C)
35
40
1.32
1.42
1.41
1.51
1.46
1.56
1.49
1.61
1.51
1.65
1.52
1.68
1.49
1.66
1.48
1.66
1.48
1.66
1.48
1.66
1.48
1.67
VLT (°C)
35
40
2.35
2.10
2.65
2.36
3.01
2.71
3.22
2.88
3.78
3.35
4.22
3.70
4.87
4.30
5.36
4.70
5.69
4.97
5.83
5.10
6.07
5.30
45
50
--
--
3.37
--
4.06
3.90
4.48
4.40
5.32
5.15
5.99
5.76
6.97
6.74
7.64
7.41
8.09
7.86
8.31
8.05
8.67
8.37
45
50
--
--
1.60
--
1.69
1.85
1.73
1.88
1.79
1.95
1.83
2.00
1.82
1.99
1.83
2.00
1.84
2.02
1.84
2.02
1.85
2.02
45
50
--
--
2.11
--
2.41
2.11
2.59
2.34
2.98
2.65
3.27
2.88
3.83
3.40
4.17
3.70
4.40
3.90
4.51
3.99
4.69
4.15
TOSHIBA I 11
TOSHIBA
55
--
--
--
4.31
4.98
5.52
6.51
7.18
7.62
7.79
8.06
55
--
--
--
2.03
2.11
2.17
2.15
2.17
2.19
2.19
2.18
55
--
--
--
2.12
2.36
2.54
3.03
3.30
3.48
3.56
3.70
I 11