Kv Test Jumper; Setpoint Operations - Ransburg 9060 Service Manual

Classic high voltage controller (hv3 - handguns)
Hide thumbs Also See for 9060:
Table of Contents

Advertisement

Figure 19: Jumper Location - Front Panel Lockout
Overload
The overload circuit may be activated for applications
that require overload indication or notification of high
current draws of the applicator. The default overload
value is set in the software to the maximum microamp
rating minus 10 microamps.
1. Turn AC power off and access the interior of the
Controller.
2. Place the jumper across the two (2) pins at location
17 on the main PC board (See Figure 20).
3. Close the Controller and turn AC power back on.
An overload fault will now occur if the microamp
display exceeds the overload value.
Figure 20: Jumper Location - Overload Activation
CP-17-02
JUMPER 16 INSTALLED FRONT
PANEL CONTROL DE-ACTIVATED
JUMPER 17 INSTALLED
OVERLOAD ACTIVATED
9060 Classic High Voltage Controller -

KV TEST JUMPER

To assist in testing and troubleshooting, a jumper (J8)
has been added to the main PC board. By covering
(shorting) both terminals of this jumper, the high volt-
age of the spray applicator can be activated. Thus, for
testing and troubleshooting, high voltage output can
be obtained without the need to trigger air through the
spray applicator. After testing, the jumper must be
repositioned so that it covers only one terminal
(open) or the high voltage will stay on all the time.
See Figure 21 for the location of test jumper J8. Ensure
the jumper is installed on ONLY ONE post during power
on to prevent a boot fault "bF". The terminals should
be shorted only when the unit is completely power on.
!
† If jumper J8 is left covering (shorting) both
terminals, the High Voltage will remain on or cause
a boot fault (bF) when the unit is powered on.
† Use Ransburg Calibrated Equipment ONLY
for testing and troubleshooting. Refer to the "Ac-
cessories" section of this manual for part numbers
for testing equipment.
Figure 21: KV Test Jumper Location

SETPOINT OPERATIONS

Voltage Setpoints
The voltage on the 9060 High Voltage Controller is
adjustable between 20 kV and full kV DC. There are 3
voltage setpoints (presets); 1, 2, and 3. Each of these
W A R N I N G
NOTE
kV TEST JUMPER
OPERATION