Dc power supply - 24v, 2.5 a, 60 w, single-phase input

Advertisement

Quick Links

DC Power Supply - 24V, 2.5 A,
60 W, Single-phase Input
Catalog Number 1606-XLB60E
Reference Manual
Original Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley 1606-XLB60E and is the answer not in the manual?

Questions and answers

Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLB60E

  • Page 1 DC Power Supply - 24V, 2.5 A, 60 W, Single-phase Input Catalog Number 1606-XLB60E Reference Manual Original Instructions...
  • Page 2 If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Table Of Contents

    Additional Resources ..........23 Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 4 Notes: Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 5: Terminology And Abbreviations

    Cost-optimized without compromising quality or reliability • Width only 36 mm (1.42 in.) • Efficiency up to 91.8% • Low no-load power losses • Full power between -10…+60 °C (14…140 °F) • Large screw terminals Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 6: Specifications

    36 x 90 x 91 mm Size (W x H x D) Without DIN rail (1.42 x 3.54 x 3.58 in.) Weight 225 g (0.49 lb) — Catalog Number Catalog Number Description 1606-XLB60BE Power supply Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 7: Ac Input

    Power Factor, Typ 1.25 A a) 100V AC b) 120V AC c) 230V AC 0.75 a: 100V AC b: 120V AC c: 230V AC 0.25 2.5 A 2.5 A Output Current Output Current Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 8: Input Inrush Current

    Figure 6 - First Inrush Peak with 2 A/DIV Input Current Figure 7 - Typical Turn-on Behavior at 230V AC and 25 °C (77 °F) Ambient Figure 8 - First Inrush Peak with 5 A/DIV Input Current Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 9: Output

    Figure 10 - Intermittent Current at Short Circuit, Typ Output Voltage Adju stment ra nge Output Current Normal Normal Short -circuit operation operation A: continuous current B: intermittent current Output Current 145 ms 145 ms 145 ms Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 10: Hold-Up Time

    Zero Transition Input Voltage a) 24V 1.25 A typ - 5% Output b) 24V 1.25 A min c) 24V 2.5 A typ Voltage d) 24V 2.5 A min Hold-up Time 230V AC Input Voltage Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 11: Efficiency And Power Losses

    Figure 15 - Efficiency Versus Input Voltage at 24V, 2.5 A, Typ Figure 16 - Losses Versus Input Voltage at 24V, 2.5 A, Typ Efficiency Power Losses 225 260V AC 225 260V AC Input Voltage Input Voltage Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 12: Functional Diagram

    DC OK status indicator (green) The status indicator is on when the output voltage is above 18V. Output voltage adjustment potentiometer Input terminals L: Phase (Line) input N: Neutral conductor input Protective Earth (PE) input Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 13: Connection Terminals

    At 24V, 1.25 A and 40 °C (104 °F) Lifetime expectancy 324 khr 370 khr 419 khr At 24V, 2.5 A and 25 °C (77 °F) 734 khr 744 khr 744 khr At 24V, 1.25 A and 25 °C (77 °F) Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 14: Mean Time Between Failure

    The device is used on AC 100V mains with more than 1.9 A load. • The application is sensitive to short output voltage dips during mains interruptions, even with a length shorter than 20 ms. Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 15 EN 61000-3-3 Fulfilled, tested with non-pulsing constant current loads. Switching frequency information is provided in the following table: Switching Frequency Value Notes Main converter 40…140 kHz Dependent on input voltage and output load Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 16: Environment

    B... T amb < 50 °C A... continuous C... T amb < 45 °C B... short term (300 s max) Altitude 2000 4000 5000 m +70 °C 54 kPa Ambient Temperature (1) Atmospheric pressure Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 17: Safety And Protection Features

    Field test 2000V AC 2000V AC 500V AC Cutoff current setting for field test — > 2 mA > 2 mA > 6 mA Figure 21 - Dielectric Strength Input Output Earth, PE Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 18: Approvals And Fulfilled Standards

    Administrative Measures for the Restriction of the Use of RoHS (China RoHS 2) Hazardous Substances in Electrical and Electronic Products 25 years EAC Certificate EAC Eurasian Conformity - Registration Russia, Kazakhstan, and Belarus Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 19: Physical Dimensions And Weight

    (0 in.) to 15 mm (0.59 in.). Penetration protection Small parts like screws and nuts with a diameter larger than 4.2 mm (0.165 in.). Figure 22 - Front View Figure 23 - Side View Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 20: Series Operation

    Such a phase-to-phase connection is allowed as long as the supplying voltage is +10% below 240V Ensure that the wire, which is connected to the N-terminal, is appropriately fused. Figure 25 - Operation on Two Phases Power Supply Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 21: Use In A Tightly Sealed Enclosure

    Do not parallel devices for higher output currents. Parallel Use for 1+1 Redundancy We recommend that you not use this power supply for 1+1 redundancy, as it does not have a DC OK monitoring function. Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 22 Notes: Rockwell Automation Publication 1606-RM119A-EN-P - July 2020...
  • Page 23: Additional Resources

    DC Power Supply - 24V, 2.5 A, 60 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Provides guidance on how to conduct security assessments, implement Rockwell System Security Design Guidelines Reference Manual,...
  • Page 24 At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.