Rockwell Automation Allen-Bradley 1606 Reference Manual

Rockwell Automation Allen-Bradley 1606 Reference Manual

Switched mode power supplies
Hide thumbs Also See for Allen-Bradley 1606:

Advertisement

Quick Links

Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLE960MX-3N
Index
1. Description ............................................................1
2. Specification Quick Reference.........................1
3. Catalog Numbers .................................................1
4. Certification Marks...............................................1
5. AC-Input..................................................................3
6. Input Inrush Current ......................................... 4
7. Output ................................................................... 5
8. Hold-up Time....................................................... 6
9. Efficiency and Power Losses .......................... 7
10. Functional Diagram ........................................... 8
11. Front Side and User Elements........................ 8
12. Terminals and Wiring ........................................ 9
13. Reliability ............................................................... 9
14. EMC....................................................................... 10
15. Environment ....................................................... 11
16. Protection Features ......................................... 12
17. Safety .................................................................... 12
18. Dielectric Strength ........................................... 12
19. Certifications ..................................................... 13
Terminology and Abbreviations
• PE and
symbol-PE is the abbreviation for Protective Earth and has the same meaning as the symbol
• Earth, Ground-This document uses the term "earth" which is the same as the U.S. term "ground".
• T.b.d.-To be defined, value or description will follow later.
• 3AC 400V-A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. 3AC means three phase input. E.g.: DC 12V describes a 12V battery whether it is charged (13.7V) or discharged (10V).
Unless otherwise stated, 3AC 400V parameters are valid at 50Hz and 3AC 480V parameters are valid at 60Hz mains frequency.
• 3x 400Vac-A figure with the unit (Vac) at the end is a value used during testing without any additional tolerance included. 3AC means three
phase input.
20. Environmental Compliance ................................... 13
21. Physical Dimensions and Weight.......................... 14
23. Accessories ................................................................... 15
Power Supply.................................................................15
25. Application Notes...................................................... 16
25.2. Charging Batteries ........................................ 16
25.3. Output Circuit Breakers ............................... 17
25.4. External Input Protection............................ 18
25.5. Back-feeding Loads ...................................... 18
25.7. Parallel Use for Redundancy...................... 18
25.8. Series Operation............................................ 19
25.10. Loss of One Input Phase............................. 19
25.12. Mounting Orientations ................................ 20
.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley 1606 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rockwell Automation Allen-Bradley 1606

  • Page 1: Table Of Contents

    Reference Manual Bulletin 1606 Switched Mode Power Supplies Catalog Number: 1606-XLE960MX-3N Index 1. Description ............1 20. Environmental Compliance ........13 2. Specification Quick Reference......1 21. Physical Dimensions and Weight......14 3. Catalog Numbers ..........1 22. Installation and Operating Instructions ..... 14 4.
  • Page 2: Description

    EMC, LVD UL 508 Accessory 1606-XLSBUFFER48 48V Buffer Unit C-Tick Marine RINA GOST R All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 3 All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 4: Ac-Input

    “Shut-down” by the red LED. 528 552 576Vac All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 5: Input Inrush Current

    Input inrush current, typical behavior Fig. 6-1 Input Current Input Voltage Output Voltage All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 6: Output

    100% higher output current for typ. 5s Zone C: Quick-acting shut-down after typ. 0.1s All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 7: Hold-Up Time

    Note: At no load, the hold-up time can be up to one minute. The green DC-ok LED is on at this time. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 8: Efficiency And Power Losses

    1606-XLE960MX-3N 95.2 Input Voltage Input Voltage 95.0 500 3x550 Vac 500 3x550 Vac All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 9: Functional Diagram

    When the fault is Earth) input cleared, the device will operate normally. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 10: Terminals And Wiring

    It is the statistical representation of the likelihood of failure of a specific unit and does not necessarily represent the life of a product. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 11: Emc

    Switching frequency Switching frequency 36kHz Nearly constant All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 12: Environment

    70° C 2000 4000 6000m The ambient temperature is defined 2cm below the unit. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 13: Protection Features

    All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 14: Certifications

    Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE), Polychlorinated Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxid e (PBDO), Cadmium, Asbestos, Mercury, Silica All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 15: Physical Dimensions And Weight

    The unit does not contain any field replaceable part. In case of damage or malfunction, turn power off immediately and return the unit to the manufacturer for inspection. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 16: Accessories

    Ease of installation Size Weight + …very, very good ++…very good +…good -…poor All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 17: Application Notes

    25.2. Charging of Batteries The power supply shall not be used to charge batteries. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 18: Output Circuit Breakers

    29mOhm. A wire no smaller than 6.0mm must be used. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 19: External Input Protection

    Monitor the individual power supply units. A DC-ok LED and a DC-ok contact are included in some redundancy modules and are able to report a faulty unit. All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 20: Series Operation

    52.9°C (in the middle of the right side of the power supply with a distance of 2cm) Temperature outside the box: 25.1°C Temperature rise: 27.8K All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 21: Mounting Orientations

    60°C Fig. 25-9 Output Power Mounting Orientation E (Horizontal ccw) Ambient Temperature 60°C All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM025A-EN-P — April 2014...
  • Page 22 Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.