Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLB60EH
Page 1
DC Power Supply - 24V, 2.5 A, 60 W, Single-phase Input Catalog Number 1606-XLB60EH Reference Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
• No PE connection required • Width only 36 mm (1.42 in.) • Efficiency up to 91.8% • Low no-load power losses • Full power between -10…+60 °C (14…140 °F) • Push-in terminals Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
36 x 90 x 91 mm Size (W x H x D) Without DIN rail (1.42 x 3.54 x 3.58 in.) Weight 225 g (0.49 lb) — Catalog Number Catalog Number Description 1606-XLB60BEH Power supply Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Power Factor, Typ 1.25 A a) 100V AC b) 120V AC c) 230V AC 0.75 a: 100V AC b: 120V AC c: 230V AC 0.25 2.5 A 2.5 A Output Current Output Current Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Figure 6 - First Inrush Peak with 2 A/DIV Input Current Figure 7 - Typical Turn-on Behavior at 230V AC and 25 °C (77 °F) Ambient Figure 8 - First Inrush Peak with 5 A/DIV Input Current Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Figure 10 - Intermittent Current at Short Circuit, Typ Output Voltage Adju stment ra nge Output Current Normal Normal Short -circuit operation operation A: continuous current B: intermittent current Output Current 145 ms 145 ms 145 ms Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Zero Transition Input Voltage a) 24V 1.25 A typ - 5% Output b) 24V 1.25 A min c) 24V 2.5 A typ Voltage d) 24V 2.5 A min Hold-up Time 230V AC Input Voltage Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Figure 15 - Efficiency Versus Input Voltage at 24V, 2.5 A, Typ Figure 16 - Losses Versus Input Voltage at 24V, 2.5 A, Typ Efficiency Power Losses 225 260V AC 225 260V AC Input Voltage Input Voltage Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
1.5 mm American Wire Gauge AWG 24…12 Wire diameter max (including ferrules) 2.3 mm (0.09 in.) Wire stripping length 10 mm (0.4 in.) Screwdriver 3 mm (0.12 in.) slotted to open the spring Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
The device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Page 14
Fulfilled, tested with non-pulsing constant current loads. Switching frequency information is provided in the following table. Type of Switching Value Notes Frequency Main converter 40…140 kHz Dependent on input voltage and output load Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
B... T amb < 50 °C A... continuous C... T amb < 45 °C B... short term (300 s max) Altitude 2000 4000 5000 m +70 °C 54 kPa Ambient Temperature (1) Atmospheric pressure Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Test or Setting Time Type test 60 s 3000V AC Routine test 2500V AC Field test 2000V AC Cutoff current setting for field test — > 2 mA Figure 21 - Dielectric Strength Input Output Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Administrative Measures for the Restriction of the Use of RoHS (China RoHS 2) Hazardous Substances in Electrical and Electronic Products 25 years EAC Certificate EAC Eurasian Conformity - Registration Russia, Kazakhstan, and Belarus Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Penetration protection Small parts like screws and nuts with a diameter larger than 4.2 mm (0.165 in.). Figure 22 - Front View Figure 23 - Side View All dimensions in mm Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Such a phase-to-phase connection is allowed as long as the supplying voltage is +10% below 240V Ensure that the wire, which is connected to the N-terminal, is appropriately fused. Figure 25 - Operation on Two Phases Power Supply Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
Do not parallel devices for higher output currents. Parallel Use for 1+1 Redundancy We recommend that you not use this power supply for 1+1 redundancy, because it does not have a DC OK monitoring function. Rockwell Automation Publication 1606-RM118A-EN-P - July 2020...
DC Power Supply - 24V, 2.5 A, 60 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Switched Mode Power Supply Specifications Technical Data, publication Provides specifications for Bulletin 1606 products and applications.
Page 22
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.