Rockwell Automation Allen-Bradley 1606-XLS960E Reference Manual

Rockwell Automation Allen-Bradley 1606-XLS960E Reference Manual

24v, 40 a single-phase input

Advertisement

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley 1606-XLS960E and is the answer not in the manual?

Questions and answers

Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLS960E

  • Page 1: Table Of Contents

    Reference Manual Power Supply Reference Manual - 24V, 40 A Single-phase Input Catalog Number 1606-XLS960E Topic Page Topic Page AC Input Front Side and User Elements Input Inrush Current DC Input Environment Output Protection Features Hold-up Time Safety Features DC-OK Relay Contact Dielectric Strength Shut-down Input Standards and Certifications...
  • Page 2 • ATEX and IECEx Approved between 85…90V AC Hold-up Time 27/27 ms Dimensions W x H x D 125 x 124 x 127 mm (4.9 x 4.88 x 5 in.) Weight 1900 g /4.2 lb. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 3: Ac Input

    (1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. (2) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. Figure 1 - Input Voltage Range Rated input range 264V AC Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 4: Input Inrush Current

    (2) Over entire temperature range, mains interruptions >1 second. Figure 5 - Typical Turn-on Behavior at Nominal Load and 25 °C (77 °F) Ambient Temperature DC Input Do not operate this power supply with DC input voltage. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 5: Output

    (4) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed value that can be achieved. The typical value is about 28.5V. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 6 Figure 8 - Bonus time vs. output power Bonus Time Output Power 120 130 140 150 170% Figure 9 - BonusPower® after input turn-on Input Voltage Output Voltage 150% Bonus Power 100% Output Power Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 7: Hold-Up Time

    As soon as the output voltage exceeds 90% of the adjusted voltage. (1) The BonusPower is available as soon as power comes on and after the end of an output short circuit or output overload. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 8: Shut-Down Input

    (via open down collector) Input OFF: I > 0.3mA ON : I < 0.1mA Option C: Shut- n.c. (via external down voltage Input OFF: U < 1V ON : U = 4 -29V Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 9: Remote Control Of Output Voltage

    A protected microcontroller inside the power supply acquires and stores operating data during the life of the unit. The data can be downloaded with a small tool and special software by the Rockwell Automation service and repair personnel, even when the unit is non-operational. The data allows for better troubleshooting.
  • Page 10: Efficiency And Power Losses

    Figure 20 - Efficiency vs. Input Voltage at 24V, 40 A, typ Figure 22 - Power Loses vs. Input Voltage at 24V, 40 A. typ Power Losses Efficiency Input Voltage Input Voltage 225 260V AC 225 260V AC Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 11: Lifetime Expectancy And Mtbf

    Converter Filter Converter Overload DC-ok Temper- Output Output Output ature Over- Power Voltage Shut- Voltage Manager Monitor down Protection DC ok DC-ok Relay Contact Shut-down Event Datalogger Shut- Input & down Remote Control Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 12: Terminal And Wiring

    Figure 24 - Daisy Chaining of Outputs Figure 25 - Using Distribution Terminals Distribution Terminals Power Power Power Power Supply Supply Supply Supply Load Load Output Output Output Output max 54 A Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 13: Front Side And User Elements

    DC-OK Status Indicator DC-OK Contact Normal mode Closed During BonusPower® Closed Overload (Hiccup mode) flashing Open Output short circuit flashing Open Temperature Shut-down flashing Open Active Shut-down input flashing Open No input power Open Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 14: Emc

    (1) Tested with constant current loads, non pulsing (2) Restrictions apply for applications in residential, commercial, and light-industrial environments, where local DC power networks according to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 15: Environment

    Figure 26 - Output Current vs. Ambient Temperature Figure 27 - Output Current vs. Altitude Allowed Output Allowed Output Current at 24V Current at 24V Altitude Ambient Temperature 70°C 2000 4000 6000 m Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 16: Protection Features

    110V AC, 50 Hz, TN-,TT-mains / IT-mains max 0.71 mA / 1.73 mA 132V AC, 60 Hz, TN-,TT-mains / IT-mains max 1.18 mA / 2.82 mA 264V AC, 50 Hz, TN-,TT-mains / IT-mains (1) Double or reinforced insulation Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 17: Dielectric Strength

    IP54 enclosure. IEC 60079-0, IEC 60079-15 Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations. Number of IECEx certificate: IECEx EPS 14.0081X Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 18: Approximate Dimensions

    50% of the rated power. Increase this clearance to 15 mm in case the adjacent device is a heat source (for example, another power supply). • A disconnecting means shall be provided for the output of the power supplies when used in applications according to CSA C22.2 No 107.1-01. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 19: Accessories

    The buffer unit does not require any control wiring. It can be added in parallel to the load circuit at any given point. Buffer units can be added in parallel to increase the output ampacity or the hold-up time. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 20: Application Notes

    Use the maximum duty cycle curve (Figure 34 on page 21) to check if the average output current is below the nominal current. • The duty cycle must be below 0.75. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 21 If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids voltage loss in adjacent circuits. Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 22 To avoid voltage dips and under-voltage situations in adjacent 24V branches that are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10 ms is necessary corresponding roughly to the ride-through time of PLCs. This requires power supplies Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 23 N+1 method. For example, five power supplies, each rated for 40 A are paralleled to build a 160 A (1) Consider twice the distance to the load (or cable length) when calculating the total wire length (+ and - wire). Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 24 The maximum allowed feed-back-voltage is 35V DC. The absorbing energy can be calculated according to the built-in large sized output capacitor that is specified in Output on page 5 Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 25 230V AC Temperature inside enclosure 68.6 °C (in the middle of the right side of the power supply with a distance of 2 cm) Temperature outside enclosure 24.3 °C Temperature rise 44.3 K Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 26 Figure 40 - Mounting Orientation C (Table-top Mounting) Output Current Ambient Temperature 60°C Figure 41 - Mounting Orientation D (Horizontal cw) Output Current Ambient Temperature 60°C Figure 42 - Mounting Orientation E (Horizontal ccw) Output Current Ambient Temperature 60°C Rockwell Automation Publication 1606-RM052A-EN-P - August 2018...
  • Page 27 Power Supply Reference Manual - 24V, 40 A Single-phase Input Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Bulletin 1606 Switched Mode Power Supplies Technical Data, publication 1606-TD002 Provides detailed specifications of the 1606 Switched Mode power supply line.
  • Page 28 How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.