5.14.10 PID control

Process control such as flow rate, air volume or pressure are possible on the inverter.
A feedback system can be configured and PID control can be performed using the terminal 2 input signal or parameter setting
value as the set point and the terminal 4 input signal as the feedback value.
Pr.
127
PID control automatic
A612
switchover frequency
128
PID action selection
A610
129
PID proportional band
A613
130
PID integral time
A614
131
PID upper limit
A601
132
PID lower limit
A602
133
PID action set point
A611
134
PID differential time
A615
553
PID deviation limit
A603
554
PID signal operation
A604
selection
575
Output interruption
A621
detection time
576
Output interruption
A622
detection level
577
Output interruption
A623
cancel level
609
PID set point/deviation
A624
input selection
Downloaded from
ManualsNet.com
Name
Initial value
9999
0
100%
1 s
9999
9999
9999
9999
9999
0
1 s
0 Hz
1000%
2
search engine
Setting range
Set the value at which control is automatically switched to PID
0 to 590 Hz
control.
9999
No PID control automatic switchover function
0, 10, 11, 20, 21,
50, 51, 60, 61, 70,
71, 80, 81, 90, 91,
Select how to input the deviation value, measured value and set
100, 101, 1000,
point, and forward and reverse action.
1001, 1010,
1011, 2000,
2001, 2010, 2011
40 to 43
Refer to
page
If a narrow proportional band is set (small parameter setting value),
the manipulated amount changes considerably by slight changes in
0.1 to 1000%
the measured value. As a result, response improves as the
proportional band becomes narrower, though stability worsens as
shown by the occurrence of hunting. Gain Kp=1/proportional band
9999
No proportional control
With deviation step input, this is the time (Ti) used for obtaining the
same manipulated amount as proportional band (P) by only integral
0.1 to 3600 s
(I) action. Arrival to the set point becomes quicker the shorter an
integral time is set, though hunting is more likely to occur.
9999
No integral control
Set the upper limit. The FUP signal is output when the feedback
0 to 100%
value exceeds this setting. The maximum input (20 mA/5 V/10 V) of
the measured value is equivalent to 100%.
9999
No function
Set the lower limit. The FDN signal is output when the measured
0 to 100%
value falls below the setting range. The maximum input (20 mA/5 V/
10 V) of the measured value is equivalent to 100%.
9999
No function
0 to 100%
Set the set point during PID control.
9999
Set point set by Pr.128.
With deviation ramp input, this is the time (Td) used for obtaining the
manipulated amount only by proportional action (P). Response to
0.01 to 10 s
changes in deviation increase greatly as the differential time
increases.
9999
No differential control
The Y48 signal is output when the absolute value of the deviation
0 to 100%
exceeds the deviation limit value.
9999
No function
The action when the upper or lower limit for a measured value input
is detected or when a limit for the deviation is detected can be
0 to 3, 10 to 13
selected. The operation for PID output suspension function can be
selected.
When the output frequency after PID calculation stays less than the
0 to 3600 s
Pr.576 setting for the time set in Pr.575 or more, the inverter
operation is suspended.
9999
No output interruption function
0 to 590 Hz
Set the frequency at which output interruption is performed.
Level at which the PID output suspension function is released. Set
900 to 1100%
"Pr.577 - 1000%".
1
The set point or deviation value is input through terminal 1.
2
The set point or deviation value is input through terminal 2.
3
The set point or deviation value is input through terminal 4.
4
The set point or deviation value is input via communication.
5
The set point or deviation value is input by the PLC function.
Description
622.
5.14 (A) Application parameters