Jog Operation - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

5.9.6

JOG operation

The frequency and acceleration/deceleration time for JOG operation can be set. JOG operation is possible in both External
operation and PU.
JOG operation can be used for conveyor positioning, test operation, etc.
Pr.
15
Jog frequency
D200
16
Jog acceleration/
F002
deceleration time
Note that these parameters are categorized as a simple mode parameter when the LCD operation panel (FR-LU08) or the
parameter unit (FR-PU07) is used. Setting of this parameter is enabled when the operation panel (FR-DU08) is connected and
"0" is set to Pr.160 User group read selection. (Refer to
*1
The Pr.20 initial value is set to 60 Hz for the FM type and to 50 Hz for the CA type.
 JOG operation using the external signals
• Operation can be started and stopped by the start signals (STF and STR signals) when the Jog operation selection (JOG)
signal is ON. (For the operation method, refer to
• While the JOGF or JOGR signal is input, Jog frequency setting (Pr.15) is used for operation. The rotation is forward while
the JOGF signal is input, and the rotation is reverse while the JOGR signal is input. (Direct JOG function)
• Use the JOG acceleration/deceleration time function (Pr.16) to set the acceleration/deceleration time for JOG operation.
• To use each signal, set the corresponding number selected from the following table in any of Pr.178 to Pr.189 (Input
terminal function selection) to assign the function to an output terminal.
Input signal
Pr.178 to Pr.189 settings
JOG
5 (Pr.185 initial value)
JOGF
57
JOGR
58
Output frequency(Hz)
Pr.15
setting range
JOG signal
Forward rotation STF
Reverse rotation STR
 JOG operation using the PU
• When the operation panel or parameter unit is in the JOG operation mode, the motor jogs only while the start button is
pressed. (For the operation method, refer to
410
5. PARAMETERS
5.9 (D) Operation command and frequency command
Downloaded from
ManualsNet.com
Initial
Name
Setting range
value
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Pr.20
Forward
rotation
Reverse
rotation
Pr.16
ON
ON
ON
search engine
Set the frequency for JOG operation.
Set the motor acceleration/deceleration time during JOG operation.
For the acceleration/deceleration time, set the time until the
*1
frequency
set in Pr.20 Acceleration/deceleration reference
frequency is reached.
The acceleration/deceleration times cannot be set separately.
page
354.)
page
162.)
Output frequency(Hz)
Pr.20
Pr.15
setting range
Time
JOGF signal
JOGR signal
page
163.)
Description
Forward
rotation
Time
Reverse
rotation
Pr.16
ON
ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents