Limitations; Installation Overview; Using A Coil Metering Device - Johnson Controls XAF Series Installation Manual

Full cased and uncased coils for cooling and heat pumps
Table of Contents

Advertisement

Table 3: Dimensions - XAU uncased upflow or
downflow coil
Dimensions
Height Width
Models
A (in.)
XAUA18AXXN1
16 5/8
XAUA24BXXN1
18 3/4
XAUB30CXXN1
21 1/4
XAUB36DXXN1
21 1/2
XAUC42EXXN1
23
XAUC48FXXN1
25
XAUC60GXXN1
29 1/4
XAUD60GXXN1
28 3/4
XAUD60HXXN1
33
Note:
Refrigerant line sizes may require larger lines
for extended line lengths. Refer to application
data part number 247077.
The adapter fitting must be field installed for
any refrigeration piping sizes not shown in the
table.
Refer to the Technical Guide for the outdoor unit
for the proper refrigeration piping size.

Limitations

Install the coil in accordance with all national and local
safety codes. See Table 4.
Table 4: Coil airflow limits
Outdoor
Coil size
unit (ton)
18
1 1/2
1 1/2
24
2
2
30
2 1/2
2 1/2
36
3
3
42
3 1/2
3
48
3 1/2
4
4
60
5
12
Installation Manual: XAF, XAH, and XAU Series - Full Cased and Uncased Coils for Cooling and Heat Pumps
Refrigerant
connections
line size
Liquid
Vapor
B (in.)
(in.)
(in.)
13
13
3/4
16
16
19 1/2
3/8
19 1/2
7/8
19 1/2
23
23
CFM limits
Minimum
Maximum
525
675
525
675
700
900
700
900
875
1125
875
1125
1050
1350
1050
1350
1225
1575
1050
1350
1225
1575
1400
1800
1600
1800
1750
2250
Johnson Controls Ducted Systems

Installation overview

1.
Before installation, review the installation aids
available in
Installation
installation, use the installation aids to verify that
tasks are completed as required. See Figure 7 for an
overview of components and their location.
2.
Install the coil metering device as required. See
Using a coil metering
3.
Install the coil. See
Installing the coil: XAF and XAH
coils
or
Installing the coil: XAU
4.
Connect the duct system. See
system.
5.
Connect the condensate drain lines. See
the condensate
drain.
6.
Connect the refrigerant lines. See
refrigerant
lines.
7.
Clean the coil. See
Cleaning the
8.
Check and adjust airflow as required. See
the air
system.
9.
Instruct the homeowner as needed. See
the
homeowner.

Using a coil metering device

You must install a piston or TXV (flex coil models) in the
field, unless you are using a coil with a factory installed
TXV or a coil equipped with an electronic expansion valve
(EEV). See
Using a coil equipped with an EEV: XAF and XAH
coils. Refer to the Technical Guide for outdoor units for
information on the piston or TXV required for the indoor
coil. It is best practice to install the piston or TXV kit before
installing the coil and brazing the refrigeration piping.
Note: Do not install the TXV sensing bulb until you
have completed the brazing and the piping has
cooled.
For TXV installation, refer to the Installation Manual
provided with the TXV kit and see
For piston installation, see
and the Schrader valve core are supplied with the outdoor
unit if applicable. Some outdoor sections require a TXV. If
using a piston instead of a TXV, install the Schrader valve
core in the suction line equalizer connection port and cap
the Schrader valve core with the plastic cap supplied. Do
not install the Schrader valve core if a TXV is installed,
because the TXV equalizer line attaches to the equalizer
connection port or suction line port.
 CAUTION
COIL UNDER PRESSURE
Verify that pressure has been released by depressing
Schrader valve core shown in Figure 1 and Figure
2. The coil requires a metering device to be added.
Refer to outdoor unit documentation for correct TXV
or piston to be used.
verification. During
device.
coils.
Connecting the duct
Connecting
Connecting
coil.
Adjusting
Instructing
Installing a
TXV.
Installing a
piston. The piston

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents