11.4 Connecting to Delta TP04 Series

Delta servo drives can be connected to Delta TP04 Series Operation Interface Panel and provide functions
including: Home, JOG operation, Position learning function, Relative position control, Absolute position
control, Monitor and parameter settings.
Parameters Setting
P1-01=1 (Position control (Pr) mode setting)
P1-47=202 (SHOM drive ORGP to perform forward homing)
P2-15=124 (Home detection position, contact: DI6)
P2-16=127 (Activate signal of home, contact: DI7)
P2-10=101 (Servo On (SON), default: DI1)
P2-11=108 (Command triggered (CTRG), default: DI2)
P2-12=111 (Position command selection (POS0), default: DI3)
P2-13=112 (Position command selection (POS1), default: DI4)
P3-02=1 (Communication protocol 7,E,1)
P3-05=2 (RS-485 serial communication)
Operation
Re-start the power to be ON again.
After Servo ready is completed, press the Servo ON key and activate the drive to be Servo ON.
Revision November 2014
Chapter 11 Application Examples ASDA-AB Series
11-9