Running Mode Description; Pcs + Genset System - Smartgen HMU8-9570 User Manual

Table of Contents

Advertisement

4.3 RUNNING MODE DESCRIPTION

4.3.1

PCS + GENSET SYSTEM

PCS supplies power for load in VSG (Virtual Synchronous Genset) mode. When storage loading
power is greater than start power of scheduled genset or battery pack SOC is lower than cutoff
discharge SOC, genset will start. If genset and storage battery pack share the load, when load power is
lower than allowed storage charge power, genset will charge the battery pack with constant voltage and
frequency of storage rated charge power. When battery pack SOC is greater than cutoff charge SOC,
genset will not charge for battery pack, genset and storage battery pack share the load (
NOTE: Converter
). When load power is lower than stop power of scheduled
droop and genset droop should be set as same
genset, genset will stop.
HMU8-9570 Hybrid Energy Controller User Manual
Page 14 of 29

Advertisement

Table of Contents
loading

Table of Contents