GAS WORKING
Fault
The burner does not start
The burner does not start and a
function lock out occurs
The burner ignites but then
blocks
The burner starts and then locks
out
After pre-purge and safety time,
the burner goes to lock-out and
the flame does not appear
The burner goes to lock-out right
after flame appearance
The burner repeats the starting
cycle without lock out
During operation, the burner
stops in lock out
Lock out when burner stops
Ignition with pulsation
Possible cause
• No electrical power supply . . . . . . . . . . . . . . . . . . . .Close all switches - Check connec-
• A limiter or safety control device is open. . . . . . . . . .Adjust or replace
• Flame control lock-out. . . . . . . . . . . . . . . . . . . . . . . .Reset control box
• Control box fuses blown . . . . . . . . . . . . . . . . . . . . . .Replace
• Erroneous electrical connections . . . . . . . . . . . . . . .Check connections
• Defective flame control . . . . . . . . . . . . . . . . . . . . . . .Replace
• No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Open the manual valve pilot gas
• Minimum gas pressure switch fails to close . . . . . . .Adjust or replace
• Air pressure switch in operating position . . . . . . . . .Adjust or replace
• Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . .Replace control box
Air pressure switch inoperative due to insufficient air pressure:
• Air pressure switch adjusted badly . . . . . . . . . . . . . .Adjust or replace
• Pressure switch pressure point pipe blocked . . . . . .Clean
is blocked
• Head wrong adjusted . . . . . . . . . . . . . . . . . . . . . . . .Adjust
• Fault in flame detection circuit . . . . . . . . . . . . . . . . .Replace flame control
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Solenoid valves VR or VS fail to open . . . . . . . . . . .Renew the coil or rectifier panel
• Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . .Increase on the regulator
• Defective ignition transformer . . . . . . . . . . . . . . . . .Replace
• Erroneous valve or transformer electrical . . . . . . . .Repeat connections
connections
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
• A cock down-line of the gas train is closed . . . . . . . .Open
• Air in pipework . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bleed air
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Max. gas pressure switch operates. . . . . . . . . . . . . .Adjust or replace
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
• Mains gas pressure is near the value to which . . . . .Reduce operating pressure
the min. gas pressure switch gas is adjusted.. . . . . .of minimum gas pressure switch.
The repeated drop in pressure which follows . . . . . .Replace the gas filter cartridge
valve opening causes temporary opening of the
pressure switch itself, the valve immediately
closes and the burner comes to a halt. Pressure
increases again, the pressure switch closes again
and the firing cycle is repeated. The sequence
repeats endlessly. And so on.
• Fault on air pressure switch . . . . . . . . . . . . . . . . . . .Replace
• Max. gas pressure switch operates. . . . . . . . . . . . . .Adjust or replace
• Flame remains in combustion head or flame . . . . . .Eliminate persistence of flame
simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .or replace control box
• Poorly adjusted head . . . . . . . . . . . . . . . . . . . . . . . .Adjust
• Poorly adjusted air damper, too much air . . . . . . . . .Adjust
• Output during ignition phase is too high . . . . . . . . . .Reduce
7