Riello DB 3 LSM C13 Installation, Use And Maintenance Instructions page 46

Dual fuel light oil/gas burner
Table of Contents

Advertisement

Available languages

Available languages

5.2
Servomotor adjustment (SQM 10)
1 - 4
: Limit switch cam (max. air damper opening)
2
: Limit switch cam (air damper closed)
3 - 5
: Minimum delivery (and ignition) position cam
6
: Positioning reading indicator
7
: Servomotor release
The servomotor contemporarily regulates, by transmission, air
delivery and pressure and delivery of the fuel being used.
It is fitted with a number of adjustable cams that action the same
number of selector switches.
Cam pos.1:
limits maximum opening of the servomotor.
Cam pos.2:
limits servomotor limit switch in the 0° position.
It is set in the factory at approx. 20° (just one
type of fuel.
Cam pos.3:
fixes the minimum modulation position.
It is set in the factory at approx. 20° (just one
type of fuel).
Cam pos.4:
limits maximum opening of the servomotor (for
mixed burners working with gas).
Cam pos.5:
limits minimum delivery. It is set in the factory
at approx. 20° (for mixed burners working with
gas).
Cam rest:
available.
Important:: the position of 130° must not be exceeded for limit
switches (cam 1 - 4).
5
Preparation for start up
CHAPTER
D1500
Fig. 17