Certification
6.1.9 Other Approvals
•
A copy of the Material Declaration is available online at
support.industry.siemens.com/cs/ww/en/view/109738831.
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
•
•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2300 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
42
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic
Information Products
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground
a
Ports
Signal Ports
DC Power Ports
https://
Test Levels
Severity Levels
±8 kV
±15 kV
20 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
RUGGEDCOM RSG2300
Installation Manual, 04/2022, C79000-G8976-1046-18
4
4
4
3
Need help?