IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
a
Only applicable to functional earth connections separated from the safety earth connection.
EMC Immunity Type Tests per IEEE 1613
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
RUGGEDCOM RSG2300
Installation Manual, 04/2022, C79000-G8976-1046-18
Test
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped
Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Voltage Dips
and Interrupts
IEC 60255-5
Dielectric Strength
HV Impulse
6.2 EMC and Environmental Type Tests
Description
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground
a
Ports
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
AC and DC
Power Ports
DC Power Ports
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Certification
Test Levels
Severity Levels
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
10 V
100 A/m
Continuous
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
2.5 kV Common
1 kV Differential
Mode @1 MHz
30 V Continuous
300 V for 1s
15%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Fail-Safe
Relay Output)
2 kV
2 kV
5 kV (Fail-Safe
Relay Output)
5 kV
4
3
5
 
3
4
3
 
 
 
 
 
 
 
43