Section 2: Installation of CAM16
January 2016, Rev. 1
11.
Table 16.
HART Connection
HART (+)
HART (-)
Figure 24
12.
13.
14.
15.
20
HART – Digital Control (Multi-Drop)
HART Control Types (9)
a.
It is important to make sure that all devices to be connected in this mode have
a different information for each device. Make sure that you connect one device
at a time while changing the addresses as to avoid having devices with the
same address on the network.
b.
Connect J5 Jumper in Multidrop Mode
CAM16 J5 Configured for Multidrop Mode
HART – Digital Control (Wireless THUM)
Refer to
Section 12
for details about the THUM wiring and configuration.
Switch ON the power to the unit.
Through LDM Menu;
a.
Set Control Mode(CO) to 7 (Network)
b.
Set the Network Adapter Parameter (nA) to 9 (HART Block Mode) or 10 (HART
Modulation Mode) (Refer LDM Flow document for navigation)
Save the settings
Pins
STC Pin 43
STC Pin 44
CAM16 J5
P2P
MDROP
CAM216 J5
MDROP
P2P
CAM216/16 IOM
Doc. Number: ECM-402-0116
CAM16 J5
P2P
MDROP
CAM216 J5
MDROP
P2P
Installation of CAM16