C O N T R O L
P U M P
OW NE R'S
OP ER ATION &
COMMIS IONING
MANUAL
Sin gle P u mp C ontr ol le r Installa tion
an d O perating Instructio ns
MOD EL: FP C- 15007 -CON
MAIN ISOLATOR
DOC: FPC-15007-CON
VER 1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FPC-15007-CON and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Matelec FPC-15007-CON

  • Page 1 OW NE R’S OP ER ATION & COMMIS IONING MANUAL Sin gle P u mp C ontr ol le r Installa tion an d O perating Instructio ns MOD EL: FP C- 15007 -CON MAIN ISOLATOR DOC: FPC-15007-CON VER 1.0...
  • Page 2: Table Of Contents

    W ELCO ME TO SINGLE PU MP C ONTROL Your Single Pump Controller reflects the superior quality and attention to detail in design, engineering and manufacturing that has distinguished MATelec Products for decades. The controller incorporates the very latest in micro-processor technology, ensuring you, the owner/operator, of many years of functional, reliable and ‘user friendly’...
  • Page 3: Installation

    INSTALLATION MOUNTING 1. Controller enclosure must be FRONT SIDE VIEW mounted in a vertical position. 2. Ensure mounting method does not compromise enclosure weather proof rating. 3. Ensure access to main isolator is Mounting Frame/ not restricted. Wall 4. Ensure cables/conduits entering MAIN ISOLATOR the panel have mechanical protection and that the penetrations are sealed and do not compromise the weather Bottom Bottom proof rating of the enclosure. WIRING CONNECTION DETAIL C O NNECT IO N FPC-15006-CON COMMON FAULT...
  • Page 4: Getting Started

    OPERA TIO N This controller can perform control functions for most Single Pump pumping applications. It is more than likely that the control parameters have already been set up for your particular application, however, hereunder you will find details of the setup and configuration options. There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and “feature”options, as per the following table: DIP Switch Position Function Off/Off Mode A: Standard typical float switch configuration (Start,Stop and High Level). No Low Level Off/On Mode B: Standard configuration plus low level (Start,Stop and High Level). On/Off Mode C: Standard configuration plus Prime Loss enabled, on Low Level (Input 1) On/On...
  • Page 5 The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below: Input 1 Input 2 Input 3 Input 4 Pump Alarm State Low Level Pump Stop Pump Start High Level Closed Open/Closed Open Open Closed Open/Closed Closed Open Closed Open/Closed Closed Closed Both On High Level (after Timeout) Closed Open/Closed Open Closed Both On High Level (after Timeout) Open Open/Closed Open...
  • Page 6 In pressure pump mode some of the optional features are disabled, including maximum run alternation, anti-seize and maximum idle timers In order to activate current loop mode the enclosure must be opened and jumper J10 moved to the “current loop enabled”...
  • Page 7: Hrh-5 Data Sheet

    Sensitivity adjustable by a potentiometer (5-100kΩ) Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separated supply voltage UNI 24.. 240 VAC/DC HRH-5 DATA SHEET Output contact 1xchangeover/SPDT 8A/250V AC1 1-MODULE, mounting onto a DIN rail Device description Supply voltage terminals Terminals for conection of...
  • Page 8 Galvanically separated supp Output contact 1xchangeove EAN code 1-MODULE, mounting onto a 8595188136396 HRH-5 /UNI Device description HRH-5 Technical parameters Functions: Supply terminals: A1 - A2 Voltage range: 24... 240 V AC/ DC (AC 50 - 60 Hz) Indication of supply voltage Input: max.
  • Page 9 Output contacts i / Silver Alloy ) Connection Monitoring of two levels Monioring of one level V DC to 131 °F) F to 158 °F) ensors) Tank with Tank with monitored level monitored level 10 terminals Function Function PUMP UP Function PUMP DOWN x 0.7˝...
  • Page 10: Circuit Diagram

    C IRCUIT D IAGRAM 415 Vac Supply MSW1 Main Isolator TOL1 415VAC Pump Contactor 3P Thermal Overload Circuit Breaker 2A 240V 240N Transformer 12Vac 12 Vac 0Vac Contactor 1 Contact or 18A 240Vac TOL1 Thermal NC Contact Switch Conductivity Conductivity Relay Relay R1/1...
  • Page 11: Notes

    NOTE S...
  • Page 12: At A Glance

    If selected (the LED indicator present for the preset time. will confirm if on) the particular AUTO FLASHING pump to Automatic A low level alarm is present. Pumping Mode ON STEADY PUMP ON Pump switched on to run. Turns pump off ON STEADY If selected (the LED indicator FAULT A pump fault/overload has will confirm if on) the pump is occurred. set to Manual Pumping Mode FLASHING A prime loss fault has occurred. DISTRIBUTED BY: INSTALLATION DATE: SERIAL NUMBER: MANUFACTURED BY MATelec AUSTRALIA EMAIL: info@matelecaustralia.com.au MATelec reserves the right to alter technical specifications without notice.