LE4020/LE4020CF Installation Manual
Figure 1-5 LE4020 Power Supply and Supervision Wiring Diagram
CONTROL PANEL
ZONE
TERMINALS
Aux Power
(See Note 1)
+
-
+
Control
Panel
EOL
Resistor
See Note 3
6
7 8
9
10
11
12
13
AUX
PGM
PGM
PGM
PGM
Z1
COM
COM
1
3
3
4
+
Communicator
The following wiring diagrams are examples of ULC Listed Fire Monitoring Installation connections.
Figure 1-6 Wiring Diagram for Fire Alarm Control Unit (with dialler) and Cellular Transmitter (Passive Com-
munication System)
Note: For PowerSeries
NEO panel refer to
Installation Guide
29002157.
For PowerSeries Pro
panel refer to Installation
Guide 29010346.
Notes:
Power for the LE4020 shall be provided from the Fire Alarm Control Unit or separately listed power
l
supply rated for the application (10-28V/700mA).
All wiring connections must be run in a metallic conduit.
l
For local supervision of the wireless transmitter, connect PGM output from LE4020/LE4020CF to one
l
zone input on the Fire Alarm Control Unit.
Dry Contact Trouble output from ULC Listed Fire Alarm Control Unit must be connected to zone input
l
on the LE4020/LE4020CF for supervison of Tip/Ring connection.
-
DSC
Supervision
Relay
See Note 2
14
15
16
17
18
DC IN
Z2
Z3
Z4
19
20
+
-
Fire Alarm
Control Unit
TIP/RING
Zone Input
Outputs
Fire
Trouble
AC Input
Notes:
1. Program the zone/point as "Supervisory" type with
keypad-only announciation when in alarm. Do NOT
use a zone/point that is normally used for 2-wire
smoke detectors.
2. The power supervision relay (RM-2) is only used
when the LE4020 is not powered by the control
panel. The relay is not required since a loss of input
power to the control panel will generate a signal to
the CMC.
3. Output 4 on the LE4020 must be set as "Active
High" (default).
4. This equipment has no mains on/off switch. The plug
of the direct plug-in power supply is intended to
serve as the disconnecting method if the equipment
must be quickly disconnected. Ensure that access to
the mains plug and associated mains socket/outlet is
never obstructed.
AUX Power
LTE/3G Cellular
(10-28V/700mA)
Transmitter
LE4020/LE4020CF
T1/R1
TIP/RING
Zone
PGM4
Inputs
Output
RM1C ULC
Relay
LE4020/LE4020CF cabinet
28
LTE and 3G
(HSPA)
PSTN