3.3 STORAGE
If the circuit breaker is to be placed in storage, maximum protection
can be obtained by keeping it in the original shipping crate. Before
placing it in storage, checks should be made to make sure that the
circuit breaker is free from shipping damage and is in satisfactory
operating condition.
The circuit breaker is shipped with its contacts open and closing
springs discharged. The indicators on the front panel should confirm
this. Insert the maintenance tool in the manual charge socket
opening (Figure Set 3.3). Charge the closing springs by pumping
the handle up and down about 36 times until a crisp metallic "click"
is heard. This indicates that the closing springs are charged and is
shown by the closing spring "charged" (yellow) indicator. Remove
the maintenance tool. Push the "manual close" button. The circuit
breaker will close as shown by the circuit breaker contacts "closed"
(red) indicator. Push the "manual trip" button. The circuit breaker
will trip as shown by the circuit breaker contacts "open" (green)
indicator. After completing this initial check, leave the closing springs
"discharged" and circuit breaker contacts "open" .
Outdoor storage is NOT recommended. If unavoidable, the outdoor
location must be well drained and a temporary shelter from sun,
rain, snow, corrosive fumes, dust, dirt, falling objects, excessive
moisture, etc. must be provided. Containers should be arranged
to permit free circulation of air on all sides and temporary heaters
should be used to minimize condensation. Moisture can cause
rusting of metal parts and deterioration of high voltage insulation.
A heat level of approximately 400 watts for each 100 cubic feet of
volume is recommended with the heaters distributed uniformly
throughout the structure near the floor.
Indoor storage should be in a building with sufficient heat and
circulation to prevent condensation. If the building is not heated, the
same general rule for heat as for outdoor storage should be applied.
50DH-VR-50AXU / 50XU / 75U / 75ARU - 600 / 1200A

3.4 APPROXIMATE WEIGHT BY TYPE

Table 4. Approximate Weight by Type
Type
50DH-VR 50AXU / 75U
50DH-VR 50XU / 75ARU
Instruction Book
IB182012EN March 2017 www.eaton.com
Replacement Circuit Breaker
Amperes
LBs
600
410
1200
425
600
420
1200
435
9