The control automatically assigns him the same user number within Partition 2.
EXAMPLE OF MULTIPLE PARTITION ACCESS
Part 1
Part 2
Part 3
User 3
User 3
Level 1
Level 4
Master
Oper B
In the above example, User 3 has MASTER authority in Partition 1 and OPERATOR B authority in Partition 2. His
user number is the same for both partitions. Note that if a user number is already being used in a partition, the system
will automatically assign a new user an unused number. Also notice that no access is allowed for this user into
Partitions 3 through 8. Attempts to access these partitions would be denied automatically.

Adding a Master, Manager, or Operator Code

During user code entry, normal key depressions at other keypads in a partition are ignored. However, panic key
depression causes an alarm and terminates user entry.
Enter Installer Code + [8] + new user no. (002-250) + new user's code Or Master or Manager Code, but the code must be
a higher level of authority than the code being changed (e.g., a Manager Code can add an Operator-level Code, but
cannot add a Master or another Manager Code). Keypad prompts for the authority level for this user.
NOTE: All references to the number of user codes pertain to the VISTA-250FBPT. The VISTA-128FBPT allows only 150
user codes.
PROMPT
User Number = 003
Enter Auth. Level
Open/Close Rep.?
0 = NO , 1 = YES
Group Bypassing?
0 = NO , 1 = YES
Access Group?
Enter 0-8
RF Button ?
0=NO , 1=YES
Multi-Access ?
0 = NO , 1 = YES
Part 4
Part 5
Part 6
Part 7
EXPLANATION
Enter the level number as follows:
1 = Master
2 = Manager
3 = Operator A
4 = Operator B
5 = Operator C
6 = Duress
Keypad then prompts for Open/Close reporting option for this user.
Press 0 (NO) or 1 (YES), depending on whether or not arming/disarming by this user will trigger
Opening and Closing reports. This prompt appears only if the Installer Code is used to add a
user.
Enter 1 (YES) to allow this user to perform group bypasses. Enter 0 (NO) this user will not be
able to perform group bypasses.
NOTE: In addition to enabling the user for group bypassing, the user must also have access to
the partition(s) containing the zones being bypassed and have global arming capability.
If access schedules have been programmed, this prompt appears. Enter the user's access
group number (1-8) if this user should have limited access to the system. Enter 0 if no access
group should be assigned.
If a 5800 Series button transmitter has been enabled for arming/disarming functions, and is not
assigned to a user, this prompt appears.
Press 0 (NO) or 1 (YES). Not used in Commercial Burg and Commercial Fire.
Press 0 (NO) if the user is to have access to this partition only. Press 1 (YES) if the user is to
have access to more than one partition. If NO, the program exits this mode. If YES, the keypad
prompts for the Global Arm option for this user.
Part 8
65