4.3 Installation of the Connection Pipe

4.3.1 Flare Processing
(1). Cut the connection pipe with the pipe cutter and remove the burrs.
(2). Hold the pipe downward to prevent cuttings from entering the pipe.
(3). Remove the flare nuts at the stop valve of the outdoor unit and inside the
accessory bag of the indoor unit, then insert them to the connection pipe, after that,
flare the connection pipe with a flaring tool.
(4). Check if the flare part is spread evenly and there are no cracks (see Fig. 4.9).
4.3.2 Bending Pipes
(1). The pipes are shaped by your hands. Be careful not to collapse them.
(2). Do not bend the pipes in an angle more than 90° .
(3). When pipes are repeatedly bent or stretched, the material will harden, making it
difficult to bend or stretch them any more. Do not bend or stretch the pipes more
than three times.
(4). When bending the pipe, do not bend it as is. The pipe will be collapsed. In this
case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 4.11, and
bend it after exposing the pipe. After bending the pipe as you want, be sure to put
DC Inverter U-match Series Cassette Type Unit
d1
Fig. 4.9
Extend the pipe by unwinding it
Fig. 4.10
90° ± 1°
×
13

Advertisement

Table of Contents
loading