4.3.5.7 Piping between branch and indoor unit ("a、c、d")
Rated capacity of indoor units:
X ((Btu/h)
X≤9500
9500<X≤17100
17100<X≤48500
48500<X≤72000
72000<X

4.4 Installation of the Connection Pipe

4.4.1 Precautions when installing the connection pipe
(1) Conform to the following principles during piping connection: Connection pipeline should be as
short as possible. The height difference between indoor and outdoor units should be as short as possible.
Keep number of bends as little as possible. The radius of curvature should be as large as possible.
(2) Weld the connection pipes between indoor and outdoor unit. Please strictly conform to the
requirements for welding process. Rosin joints and pin holes are not allowable.
(3) When laying the pipes, be careful not to deform them. The radius of bending parts should be
more than 200mm (7-7/8inch). The pipes cannot be repeatedly bent or stretched, otherwise the material
will get harden. Do not bend or stretch the pipe over three times at the same position.
(4) Please use a torque wrench to connect union nut on the indoor unit.
1) Align the expansion end of copper pipe with the center of threaded joint. Tighten the flare nuts
with your hands.
2) Tighten the flare nuts with torque wrench until you hear "click" sound.
3) Use sponge to wrap the connecting pipe and joints without thermal insulation and tie it up with
plastic tape.
4) A mounting support for the connection pipe is required.
5) The curvature degree of connection pipe should not be small, otherwise the pipe might crack.
Installation personnel should use tube bender when bending the pipe.
6) Don't forcibly stretch the pipe joint, otherwise indoor capillary or other pipes might be damaged
and lead to refrigerant leakage.
Size of connection pipe between indoor branch and indoor unit
Gas pipe mm(inch)
Φ9.52(3/8)
Φ12.7(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Φ22.2(7/8)
Fig.22
20
Ultra Heat GMV Multi VRF
Liquid pipe mm(inch)
Φ6.35(1/4)
Φ6.35(1/4)
Φ9.52(3/8)
Φ9.52(3/8)
Φ9.52(3/8)