10-1. Installation Diagram of Indoor and Outdoor Units
Flat head
wood screw
7
Battery
cover
"
!
Flat head
wood screw
Batteries
3
2
Wireless remote
control
The provided Remote Controller is a wireless type,
which also can be used as a wire.
Please see "How to Connect The Remote
Controller for Wired Operation", in case of
wired control is required.
RAS-05, 07, 10, 13E2AVG-E
RAS-16, 18E2AVG-E
C
600
D
400
E
45
F
100
• Loading Batteries
1. Remove the battery cover.
2. Insert 2 new batteries (AAA type)

10. INSTALLATION PROCEDURE

Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
5
equivalent.
Filter
7
Flat head
wood screw
4
Remote control
holder
600
600
100
100
Before installing the wireless remote controller
following the (+) and (−) positions.
Hook
1
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
Extension drain hose
(Not available,
provided by installer)
2 Wireless remote controller
- 63 -
For the rear left, bottom left and left piping
Installation
plate
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Shield pipe
Right
Rear
right
Bottom
right
Do not allow the drain hose to get slack.
Make sure to run the drain hose sloped
downward.
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm or 8 mm thick heat resisting
polyethylene foam
3 Batteries
Wall
Left
Rear
left
Bottom left
Cut the piping
hole sloped
slightly.