Func.
Name
Code
Electronic thermal warning
level
Zero speed detection level
Heat sink overheat warning
Communication speed
Modbus address
Communication parity
Communication stop bit
Communication error select
Communication error
time-out
Communication wait time
O input span calibration
OI input span calibration
Thermistor input (PTC)
span calibration
Debug mode enable
Communication selection
"C" Function
Description
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.00 to 100.0Hz
Set range is 0. to 110. C
Eight option codes:
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
76,800 bps
115,200 bps
Set the address of the inverter on the
network. Range is 1 to 247
Three option codes:
No parity
Even parity
Odd parity
Two option codes:
1 bit
2 bit
Selects inverter response to
communications error.
Five options:
Trip
Decelerate to a stop and trip
Disable
Free run stop (coasting)
Decelerates to a stop
Sets the communications watchdog timer
period.
Range is 0.00 to 99.99 sec
0.0 = disabled
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
Scale factor between the external
frequency command on terminals L–O
(voltage input) and the frequency output,
range is 0.0 to 200.0%
Scale factor between the external
frequency command on terminals L–OI
(voltage input) and the frequency output,
range is 0.0 to 200.0%
Scale factor of PTC input.
Range is 0.0 to 200.0%
Displays debug parameters.
Two option codes:
Disable
Enable <Do not set>
(for factory use)
Modbus-RTU
EzCOM
EzCOM<administrator>
68
Defaults
A
B
Initial
Units
data
90.
%
0.00
Hz
C
100.
05
baud
1
00
1
bit
02
0.00
s
0.
ms
100.0
%
100.0
%
100.0
%
00
00