Using Intelligent Output Terminals
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter outputs
a signal on that terminal when it is in Run
Mode. The output logic is active low, and is
the open collector type (switch to ground).
Option
Terminal
Code
Symbol

RUN
Valid for inputs:
Required settings
Notes:
 The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter . The start frequency
is the initial inverter output frequency when it turns
ON.
 The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name
Run Signal
11, 12, AL0 – AL2
(none)
[FW,RV]
Output
frequency
Run
signal
State
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example for terminal [11] (default output
configuration shown see
Inverter output
terminal circuit
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration see
Inverter logic
circuit board
See I/O specs on
38
1
0

start freq.
ON
Description
page
66):
RUN
CM2
RY
page
66):
RUN
AL0
AL1
AL2
Power
Load
supply
page 23, 24.
t
11