Analog Output Operation
In inverter applications it is useful to monitor the
inverter operation from a remote location or from the
front panel of an inverter enclosure. In some cases,
this requires only a panel-mounted volt meter. In other
cases, a controller such as a PLC may provide the
inverter's frequency command, and require inverter
feedback data (such as output frequency or output
current) to confirm actual operation. The analog output
terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog
GND reference. The [AM] can output inverter frequency or current output value. Note that
the voltage range is 0 to +10V (positive-going only), regardless of forward or reverse motor
rotation. Use
Func.
Code


to configure terminal [AM] as indicated below.
Description

Inverter output frequency

Inverter output current

Inverter output torque

Digital output frequency

Inverter output voltage

Inverter input power

Electronic Thermal Load

LAD frequency

Digital current monitor

Cooling fin temperature

General purpose

Option
Analog
Voltage
Output
10VDC
full scale,
2mA max
See I/O specs on page 23, 24
45
AM H
O OI L
+
-
A GND