Determining Wire and Fuse Sizes
The maximum motor current in your application determines the recommended wire size.
The following table gives the wire size in AWG. The "Power Lines" column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the "Basic System Description" on page 11. The "Signal Lines"
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor
Output
Inverter Model
kW
HP
0.2
1/4
WL200-002SFE
0.4
1/2
WL200-004SFE
0.75
1
WL200-007SFE
1.5
2
WL200-015SFE
2.2
3
WL200-022SFE
0.4
1/2
WL200-004HFE
0.75
1
WL200-007HFE
1.5
2
WL200-015HFE
2.2
3
WL200-022HFE
3.0
4
WL200-030HFE
4.0
5
WL200-040HFE
5.5
7.5
WL200-055HFE
7.5
10
WL200-075HFE
11
15
WL200-110HFE
15
20
WL200-150HFE
18.5
25
WL200-185HFE
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
terminals).
Wiring
Power Lines
2
AWG16 / 1.3mm
(75C only)
2
AWG12 / 3.3mm
(75C only)
2
AWG10 / 5.3mm
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
2
AWG12 / 3.3mm
2
AWG10/ 5.3mm
(75C only)
2
AWG6 / 13mm
(75C only)
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
12
Applicable equipment
Fuse (UL-rated, class
J, CC,G,T, 600V ,
Signal Lines
Maximum allowable
18 to 28 AWG
/ 0.14 to 0.75
2
mm
shielded
wire
(see Note 4)
current)
10A
20A
30A
10A
15A
30A
50A