VI. SERVICE DIAGNOSIS

1. ERROR CODE INDICATION

* See the controller board service manual for detailed diagnosis and remedies.
* The error and caution codes other than E1 and E2 are indicated as "EE" in the 7-segment display at the time of
occurrence. But the error history is recorded as the actual error codes in parenthesis, and a maximum of five errors
are indicated from the latest entry.
Error
Item
E1
Freeze error
E2
Defrost error
EE
Water pan
(E3)
opening error
EE
Water pan closing
(E4)
error
EE
High temperature
(E5)
error
EE
Condenser
(E9)
thermistor error
EE
Data error
(EA)
EE
Cube control
(EC)
thermistor error
EE
Water regulator
(Ed)
error
Caution
Item
EE
High pressure
(C2)
Description
Freeze backup timer (45/60 minutes)
counts up before freeze cycle completes,
and evaporator temperature is 0°C or
higher.
Defrost backup timer (30 minutes) counts
up before defrost cycle completes.
Water pan has not fully opened within
60 seconds, and 3 minutes have passed
even with opening failure control.
Unit resumes operation after 60 minutes
and repeats the above error.
[Controller board before ver. 1.6A]
Water pan has not fully closed within
60 seconds, and 3 minutes have passed
even with closing failure control.
[Controller board ver. 1.6A and later]
Water pan has not fully closed within
50 seconds, opened and started to close
again, but failed to close fully within
50 seconds.
Unit resumes operation after 60 minutes
and repeats the above error.
Evaporator temperature stays 60°C or
higher for 5 seconds or more.
Condenser thermistor circuit is open or
shorted for 2 seconds.
Model setting data memory IC is
defective.
Cube control thermistor circuit is open or
shorted for 2 seconds.
Cooling water cannot stop by water
regulator error, and thermistor senses
set point or lower temperature.
Description
[Air-cooled] Condenser thermistor
senses 63°C or higher temperature.
[Water-cooled] Pressure switch senses
2.65MPa or higher pressure.
Operation
Compressor
stops
61
Operation
Reset
Press reset
Shut down
switch
Press reset
Shut down
switch
Halt
Press reset
switch
Shut down
Halt
Press reset
switch
Shut down
Press reset
Shut down
switch
Replace
Shut down
thermistor
Replace
Shut down
controller
board
Replace
Shut down
thermistor
Press reset
Continue
switch
Reset
After 5 minutes,
condensing
temperature 50°C
or lower, pressure
1.96MPa or lower