Honeywell Home TH8110R1008/U Manual page 29

Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
Comfort
305
Heat Differential
1.0° F to 3.5° F from setpoint (in
Stage 2
0.5° F increments)
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
Comfort
305
Heat Differential
1.0° F to 4.0° F from setpoint (in
Stage 3
0.5° F increments)
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
Comfort
306
Compressor Heat
Diff. Stage 1
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
Comfort
Comfort
Comfort
29
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 2 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 2 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
Both
No
ISU 301Temperature Control Options must be set
to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 3 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 3 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 3 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
Both
No
ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and ISU 205
Geo Forced Air is set to Heating and Cooling.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 1 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 1 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
®