Voltage And Switching Capacity - Electrical Load - Fasel Elektronik FCU 00 Series Installation Instructions Manual

Table of Contents

Advertisement

2.3

Voltage and switching capacity - electrical load

Designation
Nominal voltage
Oven
1)
Evaporator
2)
Infrared
PS1 (FLE-STB)
Fan
Cabin light
Cleaning light
3)
Color light
OUT 13 ... OUT 16, C5
3)
OUT 1 ... OUT 4
3)
OUT 5 ... OUT 12
IN 1 ... IN 4, IN 9 ... 12
3)
IN 5 ... IN 8
Table 3: Technical data – voltages and switching capacity consumer
1) Only in controls with the bathing option "Sauna with humidity" (Series FCUx200 and FCUx400)
2) Only in controls with the bathing option "Infrared" (Series FCUx400). For full spectrum radiators (e.g. Vitae radiators)
with high inrush currents max. 1,5 kW
3) Optional
Installation instructions Sauna control Series FCUxx00 / Version V 2.27
Type
FCU2x00, FCU3x00, FCU4x00, FCU5x00, FCU6x00
400 V 3 N ~ 50Hz
3x 230 V~ max. 3x 3 kW (AC1) / 3x 0,55kW (AC3) / 3x 0,75kW (AC15)
230 V~ max. 3 kW (Inrush current max. 30A for 5ms)
230 V~ max. 3 kW (Inrush current max. 120A for 5ms)
230 V~ max. 60 W (Inrush current max. 30A for 5ms)
230 V~ max. 15W...120 W (Inrush current max. 10A for 5ms)
230 V~ max. 15W...120 W (Inrush current max. 10A for 5ms)
230 V~ max. 120 W (Inrush current max. 10A for 5ms)
230 V~ / max. 120 W per relay / total capacity see circuit diagram
Potential free, safety extra low voltage max. 50 V / 1 A,
230 V~ / max. 120 W per relay; total capacity see circuit diagram (Inrush
current max. 6A for 5ms)
3)
safety extra low voltage approx. 15 V, switching current approx. 10 mA ,
230 V~ 50 Hz, all inputs same phase
NOTE!
FASEL additionally offers a extension power unit for loads of 9 kW, 18
kW and 24 kW.
(Inrush current max. 30A for 5ms)
(Inrush current max. 150A for 20ms)
Technical Data
11