Specification Data - Siemens SQM50.261R1Z3 Technical Instructions

Reversing
Hide thumbs Also See for SQM50.261R1Z3:
Table of Contents

Advertisement

Technical Instructions
Document No. 155-517P25
Mar 3, 2021
Specifications
SQM5... Reversing
Actuator
Page 26
SQM5... Reversing actuator
Agency approvals
Operating voltage
Operating frequency
Power consumption
Type of motor
Duty cycle
Torque
Maximum shaft torque
AGA58.1
AGA58.2
AGA58.3
AGA58.4
AGA58.5
AGA58.7
Timings
Rotational range of operation
SQM5x.xxxxxA models
SQM5x.xxxxxx3 models
SQM5x.xxxxxx4 models
SQMSx.xxxxxx6 models
Direction of rotation
Shaft
Shaft disengagement
Number of auxiliary switches
Limit switches
Electrical rating of auxiliary switches
Mounting position
Ambient operating temperature
Shipping temperature
NEMA ratings
Connections
Switches
Boards
Dimensions
Weight
Housing
Enclosure (cover)
Motor
Disengagements
SQM5... Reversing Actuators
UL, CSA, CE
24 Vac +10%-15%
110 Vac-15% to 120 Vac +10%
220 Vac-15% to 240 Vac +10%
50 to 60 Hz
20 VA
Reversing synchronous motor
100%
See Table 1.
90 lb-in
200 lb-in
220 lb-in
270 lb-in
90 lb-in
400 lb-in
See Table 1.
0° to 160°
0° to 90°
0° to 135°
0° to 160°
Reversible
Selectable. See Table 2.
Custom versions on request
Independent, cam and drive shaft
4 switches (standard, maximum 6)
2 switches (standard)
7.5 (3) A, 250 Vac
Optional
-5°F to 140°F (-20°C to 60°C)
-58°F to 140°F (-50°C to 60°C)
NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13
Spade connectors
Screwed and spade connectors
See Figures 28 through 31.
7.3 lb (3.3 kg)
Aluminum pressure die casting
Lexan
Lock resistant
Manual for drive and cam shaft
Siemens Building Technologies, Inc.

Hide quick links: