About Advanced Features & Operation
CYCLES PER HOUR - The Cycles Per Hour setting (page 18)
monitors the number of times per hour your HVAC unit may
energize. For example, at a setting of 6 cycles per hour the HVAC
unit will only be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be temporarily overridden by pressing
the WARMER or COOLER button.
TWO STAGE OPERATION - The 2nd stage of heat (auxiliary heat)
is turned on when the room temperature is equal to or less
than: the setpoint minus the 1st stage deadband (one degree,
adjustable), minus the 2nd
stage deadband (two
degrees, non-adjustable).
FILTER ICON - The
of hours for fan run time (see above) has been achieved. This
counter keeps track of the number of hours of fan run time
whether the fan is energized in the heating or cooling modes, or
in stand alone operation.
Actual hours of
fan operation
SET
19
Press and hold the
Press RESET
FILTER
RESET FILTER button
RESET
to reset the filter
FILTER
counter to 0 and
remove the
icon from the display.
Adjust the number of
hours the blower will
run before the
icon appears on the
display. 0 = off.
Heating
Deadband
db 2
(non-adj. 2˚)
2nd Stage
1st Stage
turn on
turn on
icon will appear after a set number
Cooling
Deadband
Deadband
db 1
db 1
(adj. 1˚-6˚ )
(adj. 1˚-6˚)
Heat or Cool
1st Stage
Setpoint
turn on