Installation Instructions

• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE
THIS THERMOSTAT.
• Failure to observe safety information and comply with
instructions could result in PERSONAL INJURY, DEATH
AND/OR PROPERTY DAMAGE.
• To avoid electrical shock or damage to equipment,
disconnect power before installing or servicing and use only
wiring with insulation rated for full thermostat operating
voltage.
• Before installing this control, the Voltage Selection Switch
must be placed in the correct position. See instructions.
• To avoid potential fire and/or explosion do not use in
potentially flammable or explosive atmospheres.
• Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not
designed or controlled by PECO. You must review your
application and national and local codes to assure that your
installation will be functional and safe.
• Use copper wire only, insulate or wire nut all unused leads.
• Care should be used to avoid electrostatic discharge to the
T180 thermostat.
• This unit has configuration jumpers. You may need to
reconfigure this thermostat for your application

Applications and features

For 2 or 4 Pipe Fan Coil and On/Off Control Applications
• 7 Day, 4 Event Programmability
• System Selection: Off-Heat-Cool-Auto-Setback
• 6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
• Fan Control: 1-3 Speeds
- Cycling (Auto) or Continuous (On)
- Automatic Fan Speed Staging (TB180 models only)
Connections for:
• Fan Coil Pipe Sensor
• Remote Temperature Probe
• Occupancy Control
• Door Switch or Setback
• Condensate Overflow
Daikin IM 1019
WARNING
CAUTION
Installation Instructions

Specifications

Table 1: MT180 Programmable Thermostat Specifications
Temperature
50 to 90°F / 10 to 32°C
Set Point Range
Differential
EEPROM, No batteries required,
Memory – Back-Up
Stores settings for unlimited time
Installs on standard 4" x 4" device box
Mounting
with a 2" x 4" horizontal mud ring
Physical Dimensions
4.4"H x 5.8"W x 1.1"D
Agency Approvals
UL, UL Canada
Electrical Ratings
(see Ratings table)
Figure 1: MT180 Programmable Thermostat Dimensions