Tightening Torques; Cable Gland Clamping Range - ABB PVS-50-TL Product Manual

Table of Contents

Advertisement

T
ightening torques
To maintain the IP65 protection of the system and for optimal installation,
the following tightening torques must be used:
Component
DC input terminal block
AC output terminal block 95 mm
Signal Terminal Block 1.5 mm
Service cable gland
DC cable glands
AC cable gland M63
Ethernet cable gland (PG 21)
Ethernet cable gland (PG 16)
Protective earth terminal (external)
Protective earth terminal (internal)
C
able gland clamping range
Component
Service cable gland
DC cable glands
AC cable gland M63
Ethernet cable gland (PG 21)
Ethernet cable gland (PG 16)
95 mm
(Standard / -S version)
13
2
2
Max
2
(PG 21)
34
M32 (only Standard / -S versions)
11
16
37
(PG 21)
34
M32 (Standard / -S versions)
11
- 27 -
2 - Characteristics
20.0 Nm
20.0 Nm
2.5 Nm
7.5 Nm
8.0 Nm
10.0 Nm
7.5 Nm
5.0 Nm
11.0 Nm
11.0 Nm
13...18mm
13...21mm
25...44mm
13...18mm
10...14mm

Advertisement

Table of Contents
loading

Table of Contents