P
ower limitation messages
The following table gives the complete list of power limitation messages relating to string
inverters.
Some messages may not be used depending on the inverter model installed.
- Message on display
Name of Derating and Cause
- Signal
Power limitation:
The message indicates that the user has set an output power
limitation for the inverter.
- LIMxxx% CODE:00
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Power limitation for over-frequency:
The message indicates that the user has set a power limitation
due to over frequency in order to reduce the maximum output
power of the inverter when the grid frequency exceeds certain
- LIMxxx% CODE:01
limits.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Power limitation for over-voltage:
The message indicates that the user has set a power limitation
due to overvoltage (parameter U >(10 min)) in order to reduce the
maximum output power of the inverter when the reading of the
average grid voltage exceeds certain limits.
- LIMxxx% CODE:02
The sampling of readings is done every 10 minutes (U>(10min)).
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Anti-islanding power limitation:
The message indicates that a power limitation is active since an
"islanding" condition has been recorded.
- LIMxxx% CODE:03
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Power limitation due to low grid voltage:
The message indicates that an output power limitation may occur
since a low grid voltage (AC) condition has been recorded.
- LIMxxx% CODE:04
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
The equipment can signal possible output power limitations which may
occur on the basis of:
- settings made by the user
- settings required by the grid standard of the country of installation
- protective devices inside the inverter
The signals and the messages can only be verified using the internal
Webserver.
- 156 -
8 - Maintenance
Solution
• Check the limitation value in "Settings > Power
Reduction".
• Check the limitation value set in "Settings >
Service Power > OF Derating"
• Check the limitation value in "Settings > Service
Power > U>(10min) Der."
• If the inverter remains connected to the grid and
the limitation is active, contact customer assistance
• Check that the grid voltage is lower than the
minimal voltage. Should this condition persist,
contact the grid operator to resolve the problem.