Tightening Torques; Cable Gland Clamping Range - ABB PVS-175-TL-SX2 Product Manual

175 kw
Table of Contents

Advertisement

T
ightening torques
To maintain the IP65 protection of the system and for optimal installation,
the following tightening torques must be used:

Tightening torques

Single core AC cable gland
Single core PE cable gland
Multi core AC cable gland
Service cable gland
AC connection busbar
Protective earth point (int.)
Protective earth point (ext.)
Junction screws
Side bracket screws
Communication connector counterparts
C
able gland clamping range

Cable gland clamping range

Single core AC cable gland
Single core PE cable gland
Multi core AC cable gland
Service cable gland
11
12
M40
11
M32
12
M63
11
M25
13
bolts
22
nut
26
nut
10
20
M40
11
M32
12
M63
11
M25
13
Single-core
AC panel version
T
S
R
- 25 -
3 - Characteristics
18 Nm
25 Nm
21 Nm
12 Nm
12 Nm
0.25 Nm
33 38 39
22...32mm
18...25mm
37...53mm
10...17mm
Multi-core
AC panel version (optional)
11
R
T
S
12
5 Nm
5 Nm
5 Nm
5 Nm