Troubleshooting
Fault messages
(cont.)
Displayed fault
System characteristics
code
F.377
Burner in a fault state
F.378
Burner in a fault state
F.379
Burner in a fault state
F.380
Burner in a fault state
F.381
Burner in a fault state
F.382
Burner in a fault state
F.383
Burner in a fault state
F.384
Burner in a fault state
F.385
Burner in a fault state
88
Cause
Post-processing ionisation
current calibration: Stabili-
sation conditions for post-
calibration not reached
Flame loss during stabili-
sation or operating phase
Flame signal not present
or insufficient
Flame is lost immediately
after flame formation (dur-
ing safety time)
Flame loss during operat-
ing phase
Fault counter has excee-
ded limit.
Possible contamination of
gas line
Possible contamination of
gas line
Short circuit, signal 1, ioni-
sation current.
BCU burner control unit
faulty.
Measures
Check gas type setting. If fault re-
curs, replace BCU burner control
unit: See page 100.
Reset the appliance.
Check gas supply (gas pressure
and gas flow switch).
Check flue gas recirculation.
Check for contamination of ioni-
sation electrode and burner
gauze assembly.
Reset the appliance.
Check ionisation electrode con-
necting cable for damage and
ensure it is secure.
Check ionisation electrode, re-
place if necessary.
Reset the appliance.
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode, burner
gauze assembly:
Clearance to burner gauze as-
sembly
Contamination on electrode
Reset the appliance.
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode, burner
gauze assembly:
Clearance to burner gauze as-
sembly.
Contamination on electrode
Reset the appliance.
Reset the appliance. Work through
fault analysis using fault history.
Check gas line for contamination.
Check the gas supply pressure.
Replace gas fan if required.
Reset the appliance.
Check gas line for contamination.
Check the gas supply pressure.
Replace gas fan if required.
Reset the appliance.
Check IO electrode for earth fault.
If fault persists, replace BCU burn-
er control unit: See page 100.
Reset the appliance.