Viessmann B2TF Installation And Service Instructions Manual page 46

Gas condensing storage combi boiler with 7 inch colour touchscreen
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking and adjusting the ignition and ionisation electrodes
+1
6.5
0
A
Fig. 35
Ignition electrodes
A
Ionisation electrode
B
1. Check the electrodes for wear and contamination.
2. Clean the electrodes with a small brush (not a wire
brush) or sandpaper.
Checking the back draught safety devices
Only for multiple connections to a flue system or multi
boiler systems with a flue gas cascade.
Back draught safety device in the mixing shaft of
the burner
B
A
Fig. 36
1. Undo 2 screws and remove fan
2. Remove back draught safety device
46
+3
5
0
10
A
B
.
A
.
B
±0.5
3. Check the electrode gaps. If the gaps are not as
specified or the electrodes are damaged, replace
the electrodes and gaskets and adjust them as
required. Tighten the electrode fixing screws to a
torque of 4.5 Nm.
3. Check the damper and gasket for dirt and damage.
Replace if necessary.
4. Refit back draught safety device
Note
Observe correct installation position.
5. Refit fan
and secure with 2 screws.
A
Torque: 4.0 Nm
Back draught safety device in the flue gas connec-
tion
A
Fig. 37
.
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 222-f

Table of Contents