Viessmann B2TF Installation And Service Instructions Manual page 83

Gas condensing storage combi boiler with 7 inch colour touchscreen
Table of Contents

Advertisement

Fault messages
(cont.)
Displayed fault
System characteristics
code
F.92
Function of the relevant elec-
tronics module in emergency
mode
F.94
Function of the relevant elec-
tronics module in emergency
mode. No solar central heat-
ing backup.
F.100
Electronics modules connec-
ted to PlusBus not function-
ing
F.104
Depending on configuration
of EM-EA1 extension (DIO
electronics module)
F.142
Burner in a fault state
F.160
Burner in a fault state
F.161
Burner in a fault state
Cause
ADIO electronics module
communication error
SDIO electronics module
communication error
Voltage error PlusBus
External fault message in-
put active
Communication error,
CAN bus
Communication error,
CAN bus
BCU data memory access
error
Troubleshooting
Measures
Check setting in the commission-
ing assistant and correct if re-
quired.
Check connections and leads to
the ADIO electronics module.
Check PlusBus voltage level
(24 to 28 V).
Check subscriber number on ro-
tary switch S1 and correct if re-
quired.
Check setting in the commission-
ing assistant and correct if re-
quired.
Check connections and leads to
the SDIO electronics module.
Check PlusBus voltage level
(24 to 28 V).
Check whether the PlusBus power
supply on the HMU heat manage-
ment unit is OK: Remove all con-
nected PlusBus components and
reconnect one by one.
Check that there aren't more than
2 Vitotrol 200-E connected to the
HMU.
Check whether there is a short cir-
cuit at the PlusBus cable.
Check connected external device.
Check the fan unit for correct
function. For this, check the step-
per motor of the fan unit (refer-
ence run with mains ON).
If the fault still persists, visually
check the plug-in connections
and cables of the CAN bus.
Check further CAN bus subscrib-
ers.
If fault still persists, replace the fan
unit.
If "Connection error" is dis-
played, check the internal CAN
bus subscriber connections.
If only F.160 is displayed, check
the connections of the external
CAN bus subscribers.
Check the connecting cables for
secure seating and corrosion.
Reset the appliance.
Reset the appliance.
If fault recurs, replace BCU burner
control unit: See page 100.
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 222-f

Table of Contents