Commissioning, inspection, maintenance
Commissioning the system
Fig. 25
Affix a label in the operating instructions.
Calling up the commissioning assistant at a later
point
If you need to continue commissioning later, the com-
missioning assistant can be reactivated at any time.
Filling the heating system
Fill water
According to EN 1717 with DIN 1988-100, as a heat
transfer medium for DHW heating, the heating water
must meet fluid category ≤ 3. This requirement is met if
water of potable quality is used as heating water. For
example, if additives are used, the additive manufac-
turer must specify which category the treated heating
water comes under.
Total permissible hardness of the fill and top-up water
Total heating output
kW
50
50 to
200
>
200 to
600
>
600
>
34
(cont.)
Specific system volume
< 20 l/kW
3
3.0 mol/m
(16.8 °dH)
3
2.0 mol/m
(11.2 °dH)
1.5 mol/m
3
(8.4 °dH)
< 0.02 mol/m
3
(0.11 °dH)
Tap the following buttons:
1.
2. "Service"
3. Enter password "viservice".
4. Confirm with
.
5. "Commissioning"
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
Flush the heating system thoroughly before
filling.
Only use fill water of potable water quality.
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
20 l/kW to < 50 l/kW
3
2.0 mol/m
(11.2 °dH)
3
1.5 mol/m
(8.4 °dH)
0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
50 l/kW
3
< 0.02 mol/m
(0.11 °dH)
3
< 0.02 mol/m
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)